Table 11. IBC TB2 or TB3 Interface Connections (480V)
Terminal TB2 or
TB3
Name
Description
1
48 Vdc Battery Shunt Trip
+
Contacts used to open battery breaker or disconnect.
2
48 Vdc Battery Shunt Trip
–
3
Not Used
4
Battery Detect
Contacts used to indicate whether UPS battery breaker is open or closed.
5
Battery Detect Common
6
To Next IBC TB3-1
Contacts used to open battery breaker or disconnect on second, third, and
fourth IBCs.
7
To Next IBC TB3-2
8
Not Used
9
Not Used
10
Not Used
11
Thermal Sensor Return
Contact used to signal a battery temperature out of specification and to turn
off the battery charger to prevent thermal runaway.
12
Thermal Sensor