Installing Battery Cabinets
3-16
EATON
Powerware
®
9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual
S
164201536 Rev D
www.eaton.com/powerquality
NOTE
Two cabinet joining brackets are provided in the field kit for securing each
cabinet at the top and bottom. A small flat bracket joins the top of the cabinets and a
larger flat bracket joins the cabinets at the bottom. The small flat bracket is attached to
the cabinet tops first.
10.
Remove the left‐hand screw from the top door hinge of the UPS cabinet and the
right-hand screw from the top right door hinge of the battery cabinet.
11.
Locate the small flat bracket from the field kit. Align the holes in the small flat
bracket over the door hinge screw holes. Replace the screws in the hinges,
securing the bracket to the cabinets (see Figure 3‐9).
12.
Locate the large flat bracket from the field kit. Place one end of the bracket over
the bolt on the bottom side of the lower right‐hand hinge on the battery cabinet
and the other end over the bolt on the bottom side of the lower left‐hand hinge
on the UPS cabinet (see Figure 3‐10).
Top View
Ground Wire
Ground Studs
ÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒÒ
Existing Hinge
Existing Hinge
Front of Battery Cabinet
Front of UPS Cabinet
Front View
Bracket from Kit
Nuts from Kit