DESCRIPTION:
DATE:
DRAWING NO:
3 of 3
SHEET:
REVISION:
C
032406
BATTERY WIRING INSTALLATION NOTES
Installation Information
A-11
EATON
Powerware
®
9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual
S
164201536 Rev D
www.eaton.com/powerquality
Table E. Battery Cabinet External Wiring and Termination Requirements (UPS‐to‐Battery,
Battery‐to‐Battery, or Remote Disconnect to Battery) for Powerware 9390 Model IBC-L
UPS
Model
kVA
Battery
Type
Number
of
Cabinets
Cabinet
Position
Wire
Size
UPS to
Battery
Wire
Size
Battery to
Battery
Terminations
Torque
Nm (lb in)
Size and
Type Screw
or Bolt
40 and
50
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
1 per Pole
Supplied
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
40 and
50
Note 2
1, 2, 3,
or 4
Stand
alone
1/0
1 per Pole
1/0
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
60
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
1 per Pole
Supplied
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200
3/8
I
Hex
M10 Hex
60
Note 2
1, 2, 3,
or 4
Stand
alone
2/0
1 per Pole
2/0
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200
3/8
I
Hex
M10 Hex
80
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
1 per Pole
Supplied
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
80
Note 2
1, 2, 3,
or 4
Stand
alone
3/0
1 per Pole
3/0
1 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
100
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
2 per Pole
Supplied
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
100
Note 2
1, 2, 3,
or 4
Stand
alone
2/0
2 per Pole
2/0
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
120
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
2 per Pole
Supplied
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
120
Note 2
1, 2, 3,
or 4
Stand
alone
3/0
2 per Pole
3/0
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
160
Note 2
1, 2, 3,
or 4
Line‐up‐
and‐Match
Supplied
2 per Pole
Supplied
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
160
Note 2
1, 2, 3,
or 4
Stand
alone
250 kcmil
2 per Pole
250 kcmil
2 per Pole
2 - #2-600 kcmil
2 - 1 Bolt Mounting
42.4 (375)
22.6 (200)
3/8
I
Hex
M10 Hex
NOTE 1: All specified wire sizes are 90
_
C rated copper minimum.
NOTE 2: Replace with same type and number of original battery. Mixing battery letter designation and or sizes will
damage equipment and void warranty.