22
IZM63 / IN63 low voltage air circuit breaker
MN013014EN May 2021 www.eaton.com.cn
Section 3: Circuit breaker description and operation
1 3
5 7
9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
2 4
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95
50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
E0
1 +
OT
1B
OT
1C
AL
M
C
OT
2C
M
OD
B
N
1
+ 24
V
AL
M
2
OT
2M
G1
CM
M
1
ZIN
M
OD
G
CM
M
3
PT
VA
PT
VC
ZC
OM
M
OD
B
2C
M
M
E0
2
-
AR
CO
SC
OT
1M
2C
M
M
OT
2B
N
2
AL
M
1
AL
M
3
G2
AR
M
S
AG
N
D
ZOU
T
CM
M
2
CM
M
4
PT
VB
PT
VN
2C
MM
2C
M
M
AR
CO
AR
CO
C1
B1
C2
C3
B3
C4
C5
B5
C6
C7
B7
C8
C9
B9
C1
0
C1
1
B1
1
C1
2
LCC
LC
B
ST
1
SR1
UV
1+
A1
B2
A2
A3
B4
A4
A5
B6
A6
A7
B8
A8
A9
B1
0
A1
0
A1
1
B1
2
A1
2
LC
M
ST
2
SR
2
-
UV
2
-
Frame rating modules installed on series
IZM63 / IN63 air circuit breakers with PXR are perma-
nent and SHOULD NEVER BE REMOVED. The frame
rating module battery cover with printed I
n
rating should
not be changed without proper reprogramming of the
trip unit. The I
n
rating programmed from the factory
is displayed in the lower left hand corner of the LCD
screen whenever power is applied to the trip unit. The
I
n
displayed on the LCD reflects the actual I
n
rating of
the breaker, while the value on the battery cover is for
reference only when the LCD is not powered. The I
n
rat-
ing displayed on the LCD screen and I
n
rating printed on
the frame rating module battery cover MUST ALWAYS
AGREE.
3-4.5 Trip actuator
The low-energy trip actuator is a small electromagnetic
device that provides the necessary mechanical force to ini-
tiate the tripping action of the circuit breaker. The electronic
trip unit provides a pulse to the coil of the trip actuator,
allowing the mechanical tripping action to take place. The trip
actuator is reset by the operating mechanism.
3-4.6 Fixed high instantaneous non-adjustable trip
Series IZM63 circuit breakers have a fixed instantaneous
non-adjustable setting. This fixed instantaneous trip will initi-
ate a trip at a high current peak which depends on the circuit
breaker type and rating. This setting is always active, regard-
less of the instantaneous setting.
Figure 3-10 Secondary connector top view
3-4.7 Non-automatic device
Series IZM63 / IN63 is available in a non-automatic configura-
tion. It is derived from the corresponding IZM63 / IN63 auto-
matic breaker but does not include the trip unit, Rogowski
coil type current sensors, and the high instantaneous trip
feature. The overall dimensions and the capability of mount-
ing most accessory items are maintained. Non-automatic
device are tested in keeping with IEC 60947-2 requirements.
3-5 Secondary contacts and connection diagrams
A maximum of 96 secondary wiring connection points are
available on the standard frame circuit breaker each dedicat-
ed to a specific function. The wiring points are finger safe
with no more than two wires per terminal.