Powering down/up applications (examples)
Servicing the Network Management Module – 169
Storage is the last one to power down, its availability is maximized, and its shutdown will end 30s before the end of backup
time.
3. Set Group 1 and Group 2 to: Custom.
Applications must shutdown first so Group 1 has been set to start shutdown when on battery for 30s.
Servers must shutdown second, so Group 2 has been set to start shutdown when on battery for 210s, so 3min after the
applications.