Accessing the Network Module
Installing the Network Management Module – 19
2.4.4.1 Connecting the configuration cable
STEP 1 – Connect the Micro-B to USB cable to a USB connector on the host computer.
STEP 2 – Connect the cable to the Settings connector on the Network Module.
2.4.4.2 Manual configuration of the serial connection
STEP 1 – On the host computer, download the rndis.7z file from the website www.eaton.com/downloads and extract it.
STEP 2 – Plug the USB cable and go to Windows® Device Manager.
STEP 3 – Check the CDC Serial in the list, if it is with a yellow exclamation mark implying that driver has not been installed follow
the steps 4-5-6-7 otherwise configuration is OK.
STEP 4 – Right click on it and select Update Driver Software. When prompted to choose how to search for device driver software,
choose Browse my computer for driver software. Select Let me pick from a list of device drivers on my computer.
STEP 5 – Select the folder where you have previously downloaded the driver file Click on Next.
STEP 6 – A warning window will come up because the driver is not signed. Select Install this driver software anyway
STEP 7 – The installation is successful when the COM port number is displayed for the Gadget Serial device in the Windows®
Device Manager.
Serial driver is used to emulate a serial connection from USB.
After the card is connected to the PC, manual configuration of the driver is needed for Windows® OS to discover
the serial connection.
Summary of Contents for INDGW-M2
Page 1: ...UPS Industrial Gateway Card INDGW M2 User s Guide English 06 25 2021 2 1 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 63: ...Protection Contextual help of the web interface 63 3 5 4 1 Shutdown on power outage criteria ...
Page 65: ...Protection Contextual help of the web interface 65 Example 2 Immediate OFF ...
Page 66: ...Protection Contextual help of the web interface 66 Example 4 Custom Settings 1 ...
Page 268: ...Acronyms and abbreviations Information 268 ...
Page 276: ......