List of event codes
Information – 238
816
Warning
Compatibility failure
Compatibility OK
Service required
817
Warning
Output over current
No output over current
Reduce output load
818
Warning
Output frequency out of range
Output frequency in range
Service required
819
Warning
Output voltage too high
Output voltage OK
Service required
81A
Warning
Output voltage too low
Output voltage OK
Service required
81B
Warning
UPS Shutoff requested
End of UPS shutoff requested
Service required
81D
Warning
Load not powered
Load protected
-
900
Warning
Maintenance bypass
Not on maintenance bypass
-
901
Warning
Maintenance bypass breaker
closed
Maintenance bypass breaker open
-
B01
Warning
Batteries are aging. Consider
replacement
Batteries aging condition cleared
-
7.5.2.3 Info
Code
Severity
Active message
Non-active message
Advice
005
Info
Communication lost (with UPS)
Communication recovered (with
UPS)
Service required
009
Info
On high efficiency / On ESS mode High efficiency disabled / ESS
disabled
-
013
Info
Upgrading: limited communication End of upgrade mode
-
101
Info
On AVR (Boost)
End of AVR (Boost)
-
102
Info
On AVR (Buck)
End of AVR (Buck)
-
603
Info
Battery discharging
End of UPS battery discharge
-
63C
Info
Battery information
Battery OK
-
A00
Info
Group 1 is OFF
Group 1 is ON
-
A01
Info
Group 2 is OFF
Group 2 is ON
-
A0F
Info
Group is OFF
Group is ON
-
7.5.2.4 Good
Code
Severity
Active message
60E
Good
UPS external battery set as “No battery”
826
Good
Load powered
Alarms with a severity set as Good are not taken into account into the counter of active alarms.
Summary of Contents for INDGW-M2
Page 1: ...UPS Industrial Gateway Card INDGW M2 User s Guide English 06 25 2021 2 1 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 63: ...Protection Contextual help of the web interface 63 3 5 4 1 Shutdown on power outage criteria ...
Page 65: ...Protection Contextual help of the web interface 65 Example 2 Immediate OFF ...
Page 66: ...Protection Contextual help of the web interface 66 Example 4 Custom Settings 1 ...
Page 268: ...Acronyms and abbreviations Information 268 ...