LDAP configuration/commissioning is not working
Troubleshooting – 272
•
•
•
•
•
•
•
•
•
•
Communication will then recover, if not go to Action#2 STEP 2.
8.6.5 Action #2
Pair agent to the Network Module with automatic acceptance (recommended in case the installation is done in a secure and trusted
network).
STEP 1: Connect to the Network Module.
On a network computer, launch a supported web browser. The browser window appears.
In the Address/Location field, enter: https://xxx.xxx.xxx.xxx/ where xxx.xxx.xxx.xxx is the static IP address of the Network
Module.
The log in screen appears.
Enter the user name in the User Name field.
Enter the password in the Password field.
Click Login. The Network Module web interface appears.
STEP 2: Navigate to Protection/Agents list page.
STEP 3: In the Pairing with shutdown agents section, select the time to accept new agents and press the Start button
and Continue. During the selected timeframe, new agent connections to the Network Module are automatically trusted and
accepted.
STEP 4: Action on the agent (IPP/IPM) while the time to accepts new agents is running on the Network Module
Remove the Network module certificate file(s) *.0 that is (are) located in the folder Eaton\IntelligentPowerProtector\configs\tls.
8.7 LDAP configuration/commissioning is not working
Refer to the section
Servicing the Network Management Module>>>Commissioning/Testing LDAP
.
8.8 Modbus communication doesn't work
8.8.1 Symptoms
Communication doesn't work
8.8.2 Possible cause
Incorrect communication parameters.
Verify that the communication parameters are set to the desired settings.For Modbus TCP configuration refer to the
section
Contextual help>>>Settings>>>Modbus>>>Modbus TCP
.
For Modbus RTU configuration refer to the section
Contextual help>>>Settings>>>Modbus>>>Modbus RTU
.
RS-485 communication lines are reversed
For two-wire networks refer to the section
Installing the Network Management Module>>>Wiring the RS-485 Modbus RTU
For four-wire networks refer to the section
Installing the Network Management Module>>>Wiring the RS-485 Modbus RTU
.
If the Modbus Card is the last device installed in the network chain or the length of the network cable is excessive,
termination needs to be enabled.
For manual pairing (maximum security), go to
Servicing the Network Management Module
section and then go to STEP 2, item 1.
Servicing the Network Management Module>>>Configuring Modbus
to get configuration and
testings information.
Summary of Contents for INDGW-M2
Page 1: ...UPS Industrial Gateway Card INDGW M2 User s Guide English 06 25 2021 2 1 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 63: ...Protection Contextual help of the web interface 63 3 5 4 1 Shutdown on power outage criteria ...
Page 65: ...Protection Contextual help of the web interface 65 Example 2 Immediate OFF ...
Page 66: ...Protection Contextual help of the web interface 66 Example 4 Custom Settings 1 ...
Page 268: ...Acronyms and abbreviations Information 268 ...
Page 276: ......