Maintenance
Contextual help of the web interface – 145
•
•
•
3.8.2.5 Troubleshooting
The Network Module fails to boot after upgrading the firmware
Possible Cause
The IP address has changed.
Note: If the application is corrupt, due to an interruption while flashing the firmware for example, the boot will be done on
previous firmware.
Action
Recover the IP address and connect to the card.
Refer to
Installing the Network Management Module>>>Accessing the Network Module>>>Finding and setting the IP
Web user interface is not up to date after a FW upgrade
Symptom
After an upgrade:
The Web interface is not up to date
New features of the new FW are not displayed
An infinite spinner is displayed on a tile
Possible causes
The browser is displaying the Web interface through the cache that contains previous FW data.
Action
Empty the cache of your browser using F5 or CTRL+F5.
3.8.2.5.1 For other issues
For details on other issues, see the
section.
Summary of Contents for INDGW-X2
Page 1: ...UPS Industrial Gateway Card INDGW X2 User s Guide English 10 18 2021 2 2 3 ...
Page 23: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 24: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 27 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 28 ...
Page 35: ...Home Contextual help of the web interface 37 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 37: ...Home Contextual help of the web interface 39 3 2 7 2 2 Bypass mode 3 2 7 2 3 Battery mode ...
Page 61: ...Protection Contextual help of the web interface 63 Example 4 Custom ...
Page 62: ...Protection Contextual help of the web interface 64 Settings 1 Settings 2 ...
Page 218: ...Default settings and possible parameters Information 220 ...
Page 266: ...Acronyms and abbreviations Information 268 ...
Page 273: ......