Wiring the RS-485 Modbus RTU terminal
Installing the Network Management Module – 13
1.
2.3.5 Configuring the termination
If the INDGW card is the last device installed in the network chain or the length of the network cable is excessive, termination
needs to be enabled.
Termination is used to match impedance of a node to the impedance of the transmission line being used. When impedances are
mismatched, the transmitted signal is not completely absorbed by the load and a portion is reflected into the transmission line.
To enable the on-board termination resistor (120Ω):
Locate the termination switch that is located on the top of the Modbus Network Module.
Belden 9843-24AWG or equivalent cabling (3 twisted-pair shielded 120Ω cable with ground) is recommended.
No more than two termination points should be used in the RS-485 network.
Summary of Contents for INDGW-X2
Page 1: ...UPS Industrial Gateway Card INDGW X2 User s Guide English 10 18 2021 2 2 3 ...
Page 23: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 24: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 27 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 28 ...
Page 35: ...Home Contextual help of the web interface 37 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 37: ...Home Contextual help of the web interface 39 3 2 7 2 2 Bypass mode 3 2 7 2 3 Battery mode ...
Page 61: ...Protection Contextual help of the web interface 63 Example 4 Custom ...
Page 62: ...Protection Contextual help of the web interface 64 Settings 1 Settings 2 ...
Page 218: ...Default settings and possible parameters Information 220 ...
Page 266: ...Acronyms and abbreviations Information 268 ...
Page 273: ......