IQ 100 Series ((130/140/150) Meter
Electrical Installation
User and Installation Manual IM02601003E - July 2010 www.eaton.com 37
10. Service: Current Only Measurement (Single Phase)
Select: “3 EL WYE” (3 Element Wye) in Meter
Programming setup.
* Even if the meter is used for only amp readings, the unit requires a
Voltage reference.
Please make sure that the voltage input is attached to the meter.
AC Control Power can be used to provide the Reference Signal.