IQ 100 Series ((130/140/150) Meter
Programming the IQ 100 Series Meter Using Software
User and Installation Manual IM02601003E - July 2010 www.eaton.com 60
Configuring Communication Settings
Use this setting to configure communication settings for the meter’s RS485 Port.
NOTES:
• The settings on this screen are the current settings for communication.
• Any changes may affect communication between the meter and your PC.
Click the Communication tab. You will see the screen shown on the
right. The screen fields and acceptable entries are as follows:
COM 2 (RS485)
Address:
1 - 247
Protocol:
Modbus RTU, Modbus ASCII or DNP 3.0
Baud Rate:
9600, 19200, 38400, 57600
Response Delay:
0 - 750 (50 msec increments)
NOTE: Response Delay is the delay the meter should use before
responding to queries. If your connecting device requires a delay
before receiving information, use response delay to program the time
to wait before the meter starts responding to queries.
Configuring (System) Settings
Use this setting to configure meter password or assign a meter designation.
Click the Settings tab. You will see the screen shown on the right.
To Enable or Disable Password for Reset and/or Configuration:
•
Click the checkbox next to the option. Enabling Password
protection prevents unauthorized tampering with devices.
IMPORTANT! You must set up a password before enabling
Password Protection. Click the Change button next to Change
Password if you have not already set up a password.
To Change the Device Designation: input a new designation into
•
this field.
When you click the Change button next to Change Password
in the Settings screen, you will see the message window shown on
the right.
1. Type in the new password (0 - 9999).
2. Retype the password.
3. Click Change. The new password will be saved and the meter
will restart.
4. You can now enable the Password for Reset (Reset Max/Min Energy Settings) or Configuration
(Device Profile) by clicking the checkbox next to the option.
When a user attempts to make a change that is under Password protection, the Eaton Meter configura
-
tion software opens a message window asking for the password. If the correct Password is not entered,
the change will not take place.