Figure 2. Step 3

 cautiOn

becOme familiar with this cautiOn On pOlarity befOre  

prOceeding with steps 4 Or 5. failure tO apply the cOrrect 

pOlarity will result in damage tO the device.

Step 4: 

For a breaker 

without

 

an 1150 trip unit

, connect wires 

from spring release to secondary contact block “B” in keeping 

with markings on wires. If the breaker has an 1150 trip unit, skip 

this step and proceed directly to Step 5.

Mounting 

Plate

Hook Feet

Forward

Spring 

Release

Lock

Spring Release 

Mounts Only In 

Middle Slot

When connecting a 24 Vdc or 48 Vdc Spring 

Release Device, be certain to apply positive (+) 

voltage to the secondary terminal “B12.”

For a breaker with an 1150 trip unit and a 

24 Vdc or 48 Vdc Spring Release Device, be  

certain to apply positive voltage to secondary 

terminal “A13” for INCOM Close.

SR

B12

B13

DC Pos. (+) 

DC Neg. (–)

INCOM 

Close

A13

DC Pos. (+)

Figure 3. Step 4

Step 5: 

For a breaker 

with

 an 1150 trip unit only, find the rust-

colored connector in the vicinity of where the spring release  

device is mounted. This two-piece connector will easily separate  

by pulling apart on the two ends. Insert the spring release 

wire marked “B12” into the connector until it snaps into place. 

Re-connect the rust-colored connector. Insert the spring release  

wire “B13” into the breaker secondary block “B” at position 13.

Figure 4. Step 5

Step 6: 

Reinstall front cover removed in Step 1.

Spring 

Release

Secondary  

Block “B”

Position 12

Position 13

Rust-Colored 

Connector

Secondary  

Block “B”

Position 13