Circuit breaker accessory and installation
Closing coil
After charging, the closing coil enables the energy stored in the
operating mechanism to release instantaneously, allowing the cir-
cuit breaker to close quickly.
• IZM65/67/69
GB93 2×
4
GB97 2×
4
GB29.2 2×M4×62
Power loss table of the closing coil
Insulation
voltage
(U
i
)
Rated control
voltage U
s
(V)
Actuating
voltage
Pickup
transient
current
Pickup
transient
power
400V
AC230
(0.85~1.1) U
s
2.8A
575VA
AC400
(0.85~1.1) U
s
2.1A
780VA
AC110
(0.85~1.1) U
s
5.1A
495VA
DC110
(0.85~1.1) U
s
5.2A
550W
DC220
(0.85~1.1) U
s
2.9A
630W
Shunt Coil
The shunt coil enables the circuit breaker to open remotely.
• IZM65/67/69
GB93 2×
4
GB97 2×
4
GB29.2 2×M4×62
Power consumption of the shunt coil
Insulation
voltage
(U
i
)
Rated control
voltage U
s
(V)
Actuating
voltage
Pickup
transient
current
Pickup
transient
power
400V
AC230
(0.7~1.1) U
s
2.8A
575VA
AC400
(0.7~1.1) U
s
2.1A
780VA
AC110
(0.7~1.1) U
s
5.1A
495VA
DC110
(0.7~1.1) U
s
5.2A
550W
DC220
(0.7~1.1) U
s
2.9A
630W
Motor operator
The circuit breaker offers motor charging and automatic recharging
functions (manual charging is also available for the circuit breaker).
• IZM65/67/69
GB819 2×M4×10
GB5783 M6×60
GB93
6
GB97
6
Rated control voltage
U
s
(V)
AC230
AC400
DC110
DC220
Model code
M1
M2
M3
M4
Actuating
voltage
(0.85~1.1) U
s
(0.85~1.1) U
s
(0.85~1.1) U
s
(0.85~1.1) U
s
Power loss
2500A frame 150VA
150VA
150W
150W
4000A frame 150VA
150VA
150W
150W
6300A frame 180VA
180VA
180W
180W
Charging time (s)
5s
5s
5s
5s
Instruction Leafl et
Effective September 2022
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et