New generation IZM97, 99 low voltage air circuit breaker instruction manual
MN013010EN February 2020 www.eaton.com.cn
Section 4: Accessory devices
Overcurrent
trip switches
Mechanical
trip indicator
4-2 Internal electrical accessories
Other electrical accessories are mounted inside the circuit
breaker. They can be factory or site installed. There are two
different internally mounted accessories:
• Overcurrent trip switch (bell alarm)
• Motor operator
Overcurrent trip switch (bell alarm)—An overcurrent trip
switch (bell alarm) is an optional device that is used with an
optional pop-out indicator (Figure 4-8).
Figure 4-7 Auxiliary switch (2A/2B)
Control voltages
Contact rating inductive load (A)
250 Vac
125 Vdc
250 Vdc
10
0.5
0.25
Table 4.4 Auxiliary switch, overcurrent trip switch, and
cell switch contact ratings
Control
voltages
Operational voltage range
85-110%
Dropout volts 30-60%
Inrush/continuous power
consumption
Opening
time (ms)
24 Vdc
32 Vdc
48 Vdc
110-125 Vdc
220-250 Vdc
110-127 Vac
208-240 Vac
380-415 Vac
480 Vac
600 Vac
20-26 Vdc
27-35 Vdc
41-53 Vdc
94-138 Vdc
187-275 Vdc
94-140 Vac
177-264 Vac
323-457 Vac
408-528 Vac
510-660 Vac
7-14 Vdc
10-19 Vdc
14-29 Vdc
33-75 Vdc
66-150 Vdc
33-76 Vac
62-144 Vac
114-249 Vac
144-288 Vac
180-360 Vac
250 W/18 W
275 W/15 W
275 W/18 W
450 W/10 W
450 W/10 W
450 VA/10 VA
400 VA/10 VA
480 VA/10 VA
400 VA/10 VA
400 VA/10 VA
70
70
70
70
70
70
70
70
70
70
Required for 200 ms
Required for 400 ms
Table 4.3 Undervoltage release
Figure 4-8 Mechanical trip indicator with associated
overcurrent trip switch