background image

8

Instruction  Leaflet  

IL29C092E

Effective November 2013

Installation Instructions for KD, HKD, KDC, CKD,

CHKD, Circuit Breakers with Digitrip OPTIM

Trip Unit and Powernet and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

circuit breaker. If contamination is found, look for the

source and eliminate the problem.

4-2.

Switch circuit breaker to ON and OFF several times

to be sure that the mechanism linkages operate freely

and do not bind.  If mechanical linkages do not operate 

freely, replace circuit breaker.

4-3.

With the circuit breaker in the ON position, press 

the PUSH-TO-TRIP button to mechanically trip the cir-

cuit breaker. Trip, reset, and switch circuit breaker ON

several times.  If mechanism does not reset each time 

the circuit breaker is tripped, replace the circuit breaker.

4-4.

Check base, cover, operating handle, and handle

barrier, for cracks, chipping, and discoloration.  Circuit 

breakers should be replaced if cracks or severe discol-

oration is found.

4-5.

Check wire connecting terminals and other type

bus bar connectors for looseness or signs of overheat-

ing. Overheating will show as discoloration, melting, or

blistering of conductor insulation, or as pitting or melting

of conductor surfaces due to arcing. lf there is no evi-

dence of overheating or looseness, do not disturb or

tighten the connections. lf there is evidence of over-

heating, terminations should be cleaned or replaced.

Before re-energizing the circuit breaker, all terminations

and cable should be refurbished to the originally 

installed condition. 

4-6. Check circuit breaker mounting hardware, and tight-

en if necessary.

4-7. Exposure  to certain types of chemicals can cause 

deterioration of electrical connections.  Check area 

where circuit breaker is installed for any safety hazards, 

including personal safety and fire hazards and take

required precautionary actions.

Field Testing 

Any field testing should be done in accordance with 

applicable NEMA Standard. The operation of circuit

breakers with Digitrip OPTIM trip units can be field test-

ed periodically using the hand held OPTIMIZER (see

user manuals). 

Performance Testing for Ground Fault Trip Units 

Code Requirements

The National Electrical Code under Article 230-95-C

requires that any ground-fault protection system be per-

formance tested when first installed.  The test shall be 

conducted in accordance with approved instructions 

provided with the equipment.  A written record of this 

test shall be made and shall be available to the authority

having inspection jurisdiction.

Standards Requirements 

As a follow-up to the basic performance requirements 

stipulated by the N.E.C. as stated above, UL Standard

No. 1053 requires that certain minimum instructions 

must accompany each ground fault protection system.

These following statements plus a copy of the test 

record form illustrated in Figure 

4-1

are shipped with 

each Digitrip OPTIM trip unit. 

General Test Instructions

The interconnected system shall be evaluated in accor-

dance with the equipment assembler's detailed instruc-

tions by qualified personnel.

The polarity of the neutral sensor connections (if used)

must agree with equipment assembler's detailed instruc-

tions to avoid improper operations following apparently 

correct simulated test operations. Where a question 

exists, consult the specifying engineer and/or equipment

assembler.

The grounding points of the system shall be verified to

determine that ground paths do not exist that would

bypass the sensors. The use of high-voltage testers 

and resistance bridges may be used.

WARNING

THERE

IS A HAZARD OF ELECTRICAL SHOCK OR

BURN WHENEVER WORKING IN OR AROUND

ELECTRICAL EQLIIPMENT.  ALWAYS TURN  OFF

POWER SUPPLYING BREAKER BEFORE CON-

DUCTING TESTS.

Since Digitrip OPTIM trip units derive their operating

power from the phase currents, and not from the

neutral current, passing current through the neutral

sensor only will not properly test the ground fault

feature.

Using a low-voltage (0-24 volt), high current, ac source.

apply a test current of 125% of the Digitrip OPTIM

Ground Fault Trip Unit pick-up setting through one 

phase of the circuit breaker, as shown in Figure 4-2.

This should cause the breaker to trip in less than 1 sec-

ond, and if an alarm indicator is supplied, it should oper-

ate. Reset the breaker and the alarm indicator.  Repeat 

the test on the other two phases.

If the system is a 4-wire system with 

a

neutral current 

sensor, apply the same current as described above 

Summary of Contents for KD

Page 1: ...anual Operation 7 4 Inspection and Field Testing 7 Effective November 2013 Supersedes IL29C092D 08 11 Instruction Leaflet IL29C092E Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers w...

Page 2: ...dations Electrotechnical Commision Recommendations No warnings and cautions relating to the safety of person IEC 157 1 The OPTlM 750 and 1050 K Frame circuit nel and equipment as well as all general a...

Page 3: ...CAUTION WHEN REMOVED AND REINSTALLED THREAD FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE CARE SHOULD BE TAKEN EVERY TIME A THREAD FORIVIING SCREW IS USEDTO ENSURE THE SCREW STARTS IN THE...

Page 4: ...crew Terminal Mounting Screw Figure 2 1 Terminal lnstallation 2 3 Pole Breakers 4 Pole Breaker Circuit Figure 2 2 Circuit Breaker Mounting Bolt Drilling Plans Circuit Breaker Handle Figure 2 3 Circuit...

Page 5: ...iring connections are made on the removable male plug of the terminal block 4 If the customer requires the interlock feature in their system then the removal of the jumper between positions 2 3 is req...

Page 6: ...RSONAL INJURY MAIN TAIN ORIGINAL ELECTRICAL CLEARANCE AND CREEPAGE SPACINGS AT TERMINATIONS 2 12 Connect the control wires and power wires to their appropriate locations on the male plug of the termin...

Page 7: ...oes not affect the operation of the circuit breaker itself No circuit breaker should be reclosed until the cause of trip is known and the situation rectified PUSH TO TRIP Button The PUSH TO TRIP butto...

Page 8: ...ult Trip Units Code Requirements The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be cond...

Page 9: ...AUTION GROUND FAULT TEST RECORD FORM Ground Fault Test Records should be Retained by Those in Charge of the Building s FIELD TESTING SHOULD BE USED FOR FUNCTION AL TESTING AND NOT FIELD CALIBRATION OF...

Page 10: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 11: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 12: ...information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eat...

Reviews: