Appendix A
M-Max Series Adjustable Frequency Drive
MN04020003E—October 2013 www.eaton.com
171
PID Controller
PNU
ID
Access
Designation
Value Range
Page
FS
(P1.3)
User
Setting
RUN
ro/rw
P9.1
163
rw
PID controller
0
= Deactivated
1
= Activated for drive control
2
= Activated for external application
95
0
P9.2
118
rw
PID controllers, P gain
0.0–1000.0%
95
100.0
P9.3
119
rw
PID controller, I reset time
0.00–320.00s
95
10.00
P9.4
167
rw
PID controller setpoint, keypad
reference
0.0–100.0%
95
0.0
P9.5
332
rw
PID controller, setpoint source
0
= Keypad unit (P9.4)
1
= Fieldbus
2
= AI1
3
= AI2
95
0
P9.6
334
rw
PID controller, process variable (PV)
source (Actual value or feedback)
0
= Fieldbus
1
= AI1
2
= AI2
96
2
P9.7
336
rw
PID controller, actual value
limiting, minimum
0.0–100.0%
96
0.0
P9.8
337
rw
PID controller, actual value
limiting, maximum
0.0–100.0%
96
100.0
P9.9
340
rw
PID controller, controller
deviation
0
= Not inverted
1
= Inverted
96
0
P9.10
132
rw
PID controller, D rate time
0.00–10.0s
96
0.00
P9.11
1431
rw
PID controller, output filter,
delay time
0.00–10.0s
96
0.0
P9.12
1016
rw
Sleep mode, frequency
0.00–P6.4 Hz
96
0.00
P9.13
1018
rw
Sleep mode, wake up setpoint
0.0–100.0%
96
25.0
P9.14
1017
rw
Sleep mode, delay time
0–3600s
96
30
P9.15
1433
rw
Hysteresis, upper limit
0.0–100.0%
97
0.0
P9.16
1434
rw
Hysteresis, lower limit
0.0–100.0%
97
0.0
P9.17
1435
rw
PID controller, max. controller
deviation
0.0–100.0%
97
3.0
P9.18
1475
rw
PID controller, reference value
scaling
0.1–32.7
97
1.0
P9.19
1476
rw
PID controller, process value
scaling
0.1–32.7
97
1.0
P9.20
1478
rw
PID controller, output signal
limit
0.00–100.0%
97
100.0