Appendix A
176
M-Max Series Adjustable Frequency Drive
MN04020003E—October 2013 www.eaton.com
Second Parameter Set
Note
Factory settings dependent on specific drive selected.
PNU
ID
Access
Designation
Value Range
Page
FS
(P1.3)
User
Setting
RUN
ro/rw
P14.1
1347
X
rw
Motor rated current (2PS)
0.2 x Ie–2 x Ie
(see motor rating plate)
121
Ie
P14.2
1352
X
rw
Current limit (2PS)
0.2 x Ie–2 x Ie
121
1.5 x Ie
P14.3
1350
X
rw
Motor rated speed (2PS)
300 … 20000 min
–1
(see motor rating plate)
121
P14.4
1351
X
rw
Motor power factor (cos ) (2PS)
0.30–1.00
(see motor rating plate)
121
P14.5
1348
X
rw
Motor rated operating voltage (2PS)
180–500V
(see motor rating plate)
121
P14.6
1349
X
rw
Motor nominal frequency (2PS)
30–320 Hz
(see motor rating plate)
121
60.00
P14.7
1343
X
rw
Minimum frequency (2PS)
0.00–P14.8 Hz
121
0.00
P14.8
1344
X
rw
Maximum frequency (2PS)
P14.7–320.00 Hz
121
60.00
P14.9
1345
X
rw
Acceleration time (2PS) (acc3)
0.1–3000s
121
3.0
P14.10
1346
X
rw
Deceleration time (2PS) (dec3)
0.1–3000s
121
3.0
P14.11
1355
X
rw
V/Hz characteristic curve (2PS)
0
= Linear
1
= Squared
2
= Configurable
122
0
P14.12
1354
X
rw
Torque increase (2PS)
0
= Deactivated
1
= Activated
122
0
P14.13
1353
X
rw
Motor temperature protection
(2PS)
0
= Deactivated
1
= Alarm
2
= Fault, stop according to P6.8
122
0
P14.14
1469
X
rw
Motor ambient temperature (2PS)
–20° to 100°C
122
40
P14.15
1470
X
rw
Motor cooling factor at zero
frequency (2PS)
0.0–150%
122
40.0
P14.16
1471
X
rw
Motor thermal time constant (2PS)
1–200 min
122
45