Instruction Booklet 

IB01900002E

Effective June 2011

Instructions for Magnum DS Metal-Enclosed

Low-Voltage NEMA 3R Assemblies

 

EATON CORPORATION

 www.eaton.com

Figure 8. Roof Seam Cover.

4.3.2 Assembly Procedures

When correctly installed, both rear and front-accessible assemblies 

should conform to the following requirements:

1.  Front panels should form a straight line. When transformers and/

or other gear are included, equipment should be located in keep-

ing with the plan drawings supplied with the equipment.

2.  Vertical sections must be correctly spaced from center to center 

and plumb. A suggestion for lining up the shipping groups is to 

establish a base line a few inches in front of the assembly and 

parallel to the final location. Equalize the distances from the front 

of the shipping groups to the base line, thus making the face of 

the assembly parallel to the base line. Check each vertical sec-

tion by dropping a plumb line from the top corner of each vertical 

section. It should align with the bottom corner.

3.  The entire assembly of vertical sections should be securely fas-

tened to floor channels or base pad.

4.  Shipping groups must be securely bolted together and all bus 

and control wiring connections properly made.

After the first shipping group has been located, the second ship-

ping group should be moved into position and similarly checked. 

The shipping groups are fastened together in accordance with the 

instructions given in drawing 9253C18. This drawing is included in 

the information packet attached to the side of the switchgear assem-

bly. Should additional copies of this drawing be needed, contact your 

Eaton sales office.

4.4 Bus, Cable and Control Connections

Refer to Section 4.4.1 thru 4.4.6 of reference IB01901001E for com-

plete instructions and guidelines on various bus connections, installa-

tion of power cables, and connection of control wiring.

4.5 Traveling Circuit Breaker Lifter

The traveling overhead circuit breaker lifter is a standard device 

installed on these assemblies where an aisle-way is present.  For 

convenience the hoist assembly is shipped contained within one 

of the end shipping sections of any multi-section shipping group.  

Remove the retaining straps securing the breaker lifter hoist prior to 

use.  A ready-to use overhead lifter is shown in Figure 9.

Figure 9. Overhead Circuit Breaker Lifter.

DANGER

DO NOT STAND UNDER THE CIRCUIT BREAKER DURING HOISTING 

OPERATIONS. THE CIRCUIT BREAKER MIGHT SLIP AND CAUSE PERSONAL 

INJURY. KEEP HANDS AND TOOLS AWAY FROM SPREADER BAR, LIFTING 

HOOKS AND BREAKER. SEVERE INJURY MAY RESULT. SUDDEN MOTIONS 

ARE COMMON IN A CABLE UNDER TENSION AS IT WINDS AROUND A 

WINCH DRUM.

Spreader bars that attach to the traveling hoist for purposes of 

attaching to the circuit breaker will be shipped separately.
In assemblies where an aisle-way is not present (non-walk-in), or by 

customer request, a separate portable breaker lifter may be speci-

fied.  Portable lifting devices are recommended to only be utilized on 

smooth level surfaces.  See Figure 10 below.

4.6 Moving Parts

There are few moving parts in the stationary structures of Magnum 

DS Low-Voltage Assemblies. It is recommended that all mov-

ing parts be carefully operated by hand. This will ensure that no 

binding or damage has occurred during shipment or handling. In 

some cases, accessories may be blocked or braced for shipment. 

Thoroughly check apparatus, such as meters and relays, for forms of 

blocking or bracing which must be removed.

Summary of Contents for Magnum DS

Page 1: ...andling and Storage 4 3 Equipment Description 5 4 Installation 11 5 Inspection Testing and Maintenance 14 6 Document References 14 Effective June 2011 Instruction Booklet IB01900002E Instructions for...

Page 2: ...1 Introduction 1 1 General Information Magnum DS Metal Enclosed Low Voltage NEMA 3R Switchgear and Switchboard Assemblies are uniquely designed for use in outdoor environments or other harsh conditio...

Page 3: ...rm that all circuits are de energized before servicing 7 After maintenance be certain every current transformer second ary circuit is completely connected or shorted DANGER IF THE SECONDARY CIRCUIT OF...

Page 4: ...ial until it is certain that every item has been received in the proper condition and that certain packing material will not be required later for equipment storage Larger items such as portable trave...

Page 5: ...iptions apply to standard metal enclosed con struction and wiring Special features and control schemes are often incorporated per customer specifications These special features are evident and portray...

Page 6: ...xternal shell and the internal breaker enclosure is approximately 7 5 inches 190 mm therefore the need for a means of emergency exit is not provided Note N A unique feature of the non walk in assembly...

Page 7: ...9255C35 120 0 3047 OVERALL DEPTH 18 4 468 BUS OPENING FROM BASE 109 1 2772 105 1 2668 51 2 1301 2 0 51 4 0 102 3 9 99 2 3 58 28 6 726 FROM BASE 26 0 660 43 4 1102 AISLE WIDTH 117 1 2974 BASE 30 2 767...

Page 8: ...Assemblies EATON CORPORATION www eaton com Figure 4 Side Elevation NEMA 3R Assembly Rear Accessible without Walk in Aisle Way C C 9259C06 86 0 2185 BASE 26 0 660 28 6 726 FROM BASE 51 2 1301 2 0 51 4...

Page 9: ...ON CORPORATION www eaton com Figure 5 Side Elevation NEMA 3R Assembly Front Accessible with Walk In Aisle Way 8652C19 87 1 2211 OVERALL DEPTH 29 1 740 111 4 2830 107 9 2740 2 0 51 3 9 99 111 5 2832 OV...

Page 10: ...d Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 6 Side Elevation NEMA 3R Assembly Front Accessible without Walk In Aisle Way 8652C25 54 2 1378 BASE 105 1 2669 110 3 2800 109 8...

Page 11: ...tion to avoid distortion of the structure The lifting plates attached at the base perform the dual purpose of providing a convenient and robust method of securing the unit to the foundation A separate...

Page 12: ...n sales office 4 4 Bus Cable and Control Connections Refer to Section 4 4 1 thru 4 4 6 of reference IB01901001E for com plete instructions and guidelines on various bus connections installa tion of po...

Page 13: ...900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Figure 10 Circuit Breaker Installation with Portable Breaker Lifter...

Page 14: ...pment Please inspect the packet attached to the outside or within an empty cell for all pertinent documentation before contact ing an Eaton service representative for replacements 2A97855 Magnum DS St...

Page 15: ...15 Instruction Booklet IB01900002E Effective June 2011 Instructions for Magnum DS Metal Enclosed Low Voltage NEMA 3R Assemblies EATON CORPORATION www eaton com Notes...

Page 16: ...ment between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the...

Reviews: