background image

8

Instructional Booklet 

IB013003EN

Effective June 2023

Instructions for installation, operation,  

and maintenance of Magnum MR2  

(integral racking) 

EATON

 www.eaton.com

Diagnostics/troubleshooting

The integrated racking controller programming has built-in 

diagnostics and error detection .  If an error occurs, “E1” to “E8” will 

appear on the pendant display (see Figure 20) .  On the back of the 

pendant there is a label that explains the error code and what to do 

if the error occurs (see Figure 22) .

Figure 20. Pendant with open/close.

Figure 21. Pendant without open/close.

Figure 22. Pendant error code descriptions.

m

 CAUTION

THERE ARE NO SERVICEABLE PARTS INSIDE THE CASE OF THE PENDANT. 

ATTEMPTING A MODIFICATION OR REPAIR OTHER THAN THOSE EXPLAINED 

IN THIS SECTION COULD EXPOSE PERSONNEL TO SHOCK HAZARD FROM 

INTERNAL CAPACITORS.  OPENING THE CASE OF THE PENDANT TO 

ATTEMPT A REPAIR WILL VOID THE WARRANTY.

E1: Motor overcurrent

Condition when motor current is in excess of allowed value .  E1 

error codes may occur if there is an obstruction in the cell .  Operator 

should shut off power to the MR2 controller by tripping the circuit 

breaker or fuse protecting the controller and manually rack out 

the Magnum breaker .   The operator should inspect the Magnum 

breaker, cassette, levering system subassembly, and controller card 

for obvious damage or abnormal conditions .  If no obvious issues are 

found, check for Magnalube on the primary disconnects and then 

reinstall the Magnum breaker .

E2: Open motor circuit

Can occur due to an excessive duty cycle (more than three 

consecutive full racking cycles in quick succession without stopping . 

one cycle=rack in and rack out) .  Once limit is reached, the E2 code 

will be displayed for two minutes, allowing the motor to cool .  After 

the cool down period, the controller can be reset by pressing the 

“Enable” and “Disconnect” buttons on the pendant, or over Modbus 

RTU communications .

E3: Motor timed out

Condition when motor continues to run in excess of the normal 

required time to reach the desired position .  This error state 

condition can be caused from a malfunction of the MR2 .  Operator 

should shut off power to the MR2 controller by tripping the circuit 

breaker or fuse protecting the controller and manually rack out the 

Magnum breaker .  Once the Magnum breaker is removed from the 

compartment, the operator can replace the damaged devices .

E4: Magnum breaker position “unknown”

Controller does not know the location of the Magnum breaker in the 

breaker compartment .  The operator must press the “Enable” and 

the “Disconnect” buttons on the pendant as the other buttons will 

not function .  Once the breaker has reached the disconnect position, 

the “Disconnect” LED will illuminate and the operator can start the 

Magnum breaker racking process again by pressing the “Connect” 

or “Test” button and the “Enable” button .

E5: Open permissive

This state is due to a permissive contact being open .  It could be 

a standard permissive such as the racking door is lifted, the  circuit 

breaker being closed, or the padlock slider being pushed in .  This 

could also be a customer supplied permissive such as a door 

interlock or a cell switch from another cell to provide interlocking . In 

this case, press the “Enable” and “Disconnect” buttons to reset the 

controller .  Once the permissive switch is closed, any operation will 

work .

E6: Communication error

This state may result from damaged communication cable or wiring .  

Check all areas of communication wiring (e .g ., discrete, CAT5, or 

Modbus controller wiring) .  This state may also occur when a breaker 

is not inserted into the compartment .  Check to make sure the 

breaker is fully pushed into the disconnect position and the tertiaries 

make good electrical connection (see Figure 3) .

E8: Position switch error

This state occurs when a breaker is not inserted into the 

compartment .  Check to make sure the breaker is fully pushed 

into the disconnect position and the tertiaries make good electrical 

connection (see Figure 3) .

MR2 error code display

Summary of Contents for Magnum MR2

Page 1: ...ndication 5 Setting the breaker type 6 Setting the Modbus address 6 Control options 7 Option 1 7 Option 2 7 Option 3 7 Sequence of operations 7 Diagnostics troubleshooting 8 E1 Motor overcurrent 8 E2 Open motor circuit 8 E3 Motor timed out 8 E4 Magnum breaker position unknown 8 E5 Open permissive 8 E6 Communication error 8 E8 Position switch error 8 Controller diagnostic display 9 Controller mount...

Page 2: ...NNEL WITH THIS TYPE OF PRESENTATION THIS WILL HELP ASSURE THAT PERSONNEL ARE ALERT TO THESE TYPES OF MESSAGES IN ADDITION THESE MESSAGES ARE ALL UPPERCASE AND BOLDFACE All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further information is desired by the purchaser re...

Page 3: ...trol the system by means of a pendant Modbus master such as the Eaton Power Distribution Monitoring and Control system or separately wired I O buttons Controller can be mounted to the left side preferred or right side of the cassette If placed in other areas of the switchgear extension wires can be added with the existing terminal blocks The eight MR2 tertiary wires connect the controller to the M...

Page 4: ...e are three methods to restrict racking a Magnum circuit breaker Option 1 lockout tagout This option prevents both electrical and manual operation Push the padlock slider forward towards the breaker aligning two holes on the left side and insert a padlock see Figure 7 The MR2 will be disabled via the permissive circuit and manual racking is blocked as well The label on the levering door will show ...

Page 5: ...acking Racking indication While electrical or manual racking there exists three discrete colored positions which are disconnect green test yellow and connect red see positions A B and C in Figure 12 At these positions the breaker can be closed when the racking door is fully lowered Figure 12 Discrete colored positions If racking is stopped electrically or manually in between disconnect test or tes...

Page 6: ...available Modbus addresses are 01 to 99 for one RS485 network To set the Modbus address follow the steps below 1 Connect pendant to the controller to be programmed 2 Hold down the Intermediate button and within three seconds press and hold the Connect button until the two digit LED display begins to flash at the same time the Connect LED will begin to flash 3 Now the Test and Disconnect buttons ca...

Page 7: ...ch of the control options Pendant I O and Modbus The Enable button must be held to operate the pendant 1 Insert the breaker into the breaker cell a The breaker is now in the disconnect position b The solid green disconnect LED will be illuminated c To proceed further and rack the breaker to the connected position the breaker must be open If the breaker is closed you will see an E5 code Refer to th...

Page 8: ...communications E3 Motor timed out Condition when motor continues to run in excess of the normal required time to reach the desired position This error state condition can be caused from a malfunction of the MR2 Operator should shut off power to the MR2 controller by tripping the circuit breaker or fuse protecting the controller and manually rack out the Magnum breaker Once the Magnum breaker is re...

Page 9: ...RI RO OC AD 1 2 3 4 5 6 7 8 1 Product group 2 Gear type will always be 02 for Magnum 3 Controller firmware version 4 Pendant firmware version 5 Rack in count 6 Rack out count 7 Overcurrent count 8 Modbus address 01 to 99 Controller mounting The controller can be mounted to the left side or right side of the cassette If placed in other areas of the switchgear extension wires can be added with the e...

Page 10: ...ube is not present please contact Eaton Technical Support and order with style shown in Table 3 Magnalube can be added to the leading edges and surfaces on all primary disconnects that make contact with the cassette stabs Table 3 Greases used on Magnum PXR and PD SB Grease type Desription Magnalube G Eaton standards 53701AI Color Green Manufactured by Saunders Enterprises inc 11 51 44th Road Long ...

Page 11: ...11 Instructional Booklet IB013003EN Effective June 2023 Instructions for installation operation and maintenance of Magnum MR2 integral racking EATON www eaton com Notes ...

Page 12: ...een the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAG...

Reviews: