background image

9

Instruction Booklet 

IB01900004E

Effective July 2016

Magnum breaker remote 

racking device (MRR1000) 

  

EATON

 www.eaton.com

Figure 9. MRR1000 operating pendant

Figure 10. Magnum DS position indicator

CAUTION

THE MOTOR DOES NOT HAVE AUTOMATIC SHUT-OFF. ONCE THE BREAKER 

LEVERING DEVICE REACHES THE END OF ITS TRAVEL, THE MOTOR WILL 

CONTINUE TO TURN WHILE THE SHAFT/CLUTCH MECHANISM (FIGURE 11) 

WILL COMPENSATE FOR THE INCREASED TORQUE BY SLIPPING BETWEEN 

THE SHAFT AND MOTOR. CONTINUING TO OPERATE THE MOTOR FOR AN 

EXTENDED PERIOD PAST THE OPERATING LIMITS WILL CAUSE EXCESSIVE 

WEAR ON THE CLUTCH AND MAY PREMATURELY SHORTEN THE LIFE OF 

THE REMOTE RACKING UNIT.

8. 

Withdraw the shaft/motor assembly from the drive socket by 

pulling rearward on the handle . If the shaft seems to bind with 

the drive socket, utilize the “JOG IN” or “JOG OUT” buttons 

described in Step 4 .3 .2 above to free the shaft .

9. 

The levering device access door will close . If the door does not 

close, the breaker is not fully in the “DISCONNECT” position .

10. 

While supporting the weight of the MRR1000, pull out the 

locking pin (

Figure 2

) to release the locking handle and rotate  

the handle rearward . The unit can now be removed from the 

circuit breaker .

CAUTION

ALWAYS REMOVE THE REMOTE RACKING DEVICE FROM THE BREAKER 

WHEN NOT IN USE. 

Figure 11. MRR1000 shaft/clutch mechanism

Summary of Contents for Magnum MRR1000

Page 1: ...ption Page Section 1 Introduction 3 Section 2 Safe practices for power circuit breakers 5 Section 3 Receiving handling and storage 5 Section 4 Procedures 6 Section 5 Warranty 12 Section 6 Troubleshoot...

Page 2: ...THIS DEVICE THE CIRCUIT BREAKERS DESCRIBED IN THIS MANUAL ARE DESIGNED AND TESTED TO OPERATE WITHIN THEIR NAMEPLATE RATINGS OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL RESULTIN...

Page 3: ...rc flash exposure PPE for high levels of arc flash can be bulky hot and uncomfortable This may dissuade personnel from wearing proper protection The best way to limit exposure to arc flash during the...

Page 4: ...klet IB01900004E Effective July 2016 Magnum breaker remote racking device MRR1000 EATON www eaton com A shaft inch mm B handle inch mm Retracted position 2 75 69 85 4 28 108 71 Extended position 4 75...

Page 5: ...quipment during shipment and storage and at the same time to provide convenient handling 3 1 Receiving Until the MRR1000 unit is ready to be delivered to the point of use do not remove it from the shi...

Page 6: ...n until use of pendant buttons as described in Steps 4 3 3 and 4 4 3 below 4 3 Procedure for removing a power circuit breaker 4 3 1 Installation on the circuit breaker face 1 The face of a typical Mag...

Page 7: ...e weight of the MRR1000 rotate the locking handle forward until it clicks into place Figure 5 Figure 4 MRR1000 attachment to breaker Figure 5 MRR1000 locking handle engaged m WARNING FAILURE TO FULLY...

Page 8: ...status of the unit 3 Using the remote operation pendant Figure 9 move an acceptable distance a away from the unit The maximum extension of the control cord is 25 ft 7 6 m Ensure the operator will be a...

Page 9: ...CESSIVE WEAR ON THE CLUTCH AND MAY PREMATURELY SHORTEN THE LIFE OF THE REMOTE RACKING UNIT 8 Withdraw the shaft motor assembly from the drive socket by pulling rearward on the handle If the shaft seem...

Page 10: ...on as indicated by the position indicator on the front of the circuit breaker Figure 10 NOTICE FOR COMPLETE INSTRUCTIONS ON INSTALLATION OPERATION AND MAINTENANCE OF THE MAGNUM DS FAMILY OF CIRCUIT BR...

Page 11: ...ched to the face of the breaker per the steps outlined in other portions of this instruction booklet 4 5 2 Operation 1 The levering device access door on the face of the breaker must be closed for any...

Page 12: ...IES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION R...