MaGnuM PRoDuct GuiDe
CA013002EN—April 2017 www.eaton.com
30
Magnum SB - Product specific information
Magnum SB - Continuous amperage, interruption and withstand ratings tables
Table 8 . Magnum DS switchgear class UL 1066 low voltage power circuit breakers ANSI
Frame
amperes
breaker
type
catalog
position
1–6
Frame
type
rms Symmetrical current ratings ka 50/60 Hz
available
current
sensor
and rating
plugs for
digitrip rms
trip unit
(establishes
breaker i
n
rating)
Poles
available
interruption
rating at
254 Vac
interruption
rating at
508 Vac
interruption
rating at
635 Vac
Short
time
Withstand
rating
Fixed
internal
inst trip
800
SBN-508
Narrow
50
50
35
20
18xI
n
200, 250, 300,
400, 600, 800
3 & 4
SBN-608
Narrow
65
65
42
20
18xI
n
3 & 4
SBN-C08
Narrow
100
100
65
20
18xI
n
3 & 4
SBS-608
Standard
65
65
65
20
18xI
n
3 & 4
SBS-808
Standard
85
85
85
20
18xI
n
3 & 4
SBS-C08
Standard
100
100
85
20
18xI
n
3 & 4
SBS-H08
Standard
130
130
130
20
18xI
n
3
SBS-E08
Standard
200
150
65
30
30
3
1200
SBN-512
Narrow
50
50
35
25
18xI
n
200, 250, 300,
400, 600, 800,
1000, 1200
3 & 4
SBN-612
Narrow
65
65
42
25
18xI
n
3 & 4
SBN-C12
Narrow
100
100
65
25
18xI
n
3 & 4
SBS-612
Standard
65
65
65
25
18xI
n
3 & 4
SBS-812
Standard
85
85
85
25
18xI
n
3 & 4
SBS-C12
Standard
100
100
85
25
18xI
n
3 & 4
SBS-H12
Standard
130
130
130
25
18xI
n
3
SBS-E12
Standard
200
150
65
30
30
3
1600
SBN-516
Narrow
50
50
35
30
18xI
n
200, 250, 300,
400, 600, 800,
1000, 1200,
1600
3 & 4
SBN-616
Narrow
65
65
42
30
18xI
n
3 & 4
SBN-C16
Narrow
100
100
65
30
18xI
n
3 & 4
SBS-616
Standard
65
65
65
30
18xI
n
3 & 4
SBS-816
Standard
85
85
85
30
18xI
n
3 & 4
SBS-C16
Standard
100
100
85
30
18xI
n
3 & 4
SBS-H16
Standard
130
130
130
30
18xI
n
3
SBS-E16
Standard
200
150
65
30
30
3
2000
SBN-620
Narrow
65
65
65
35
18xIn
200, 250, 300,
400, 600, 800,
1000, 1200,
1600, 2000
3 & 4
SBN-C20
Narrow
100
100
65
35
18xIn
3 & 4
SBS-620
Standard
65
65
65
35
18xIn
3 & 4
SBS-820
Standard
85
85
85
35
18xIn
3 & 4
SBS-C20
Standard
100
100
85
35
18xIn
3 & 4
SBS-H20
Standard
130
130
130
35
18xIn
3
SBS-E20
Standard
200
150
65
30
30
3
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit .
These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15 second interval and a close-open operation,
in succession, with delayed tripping in case of short-delay devices . The standard duty cycle for short time ratings consists of maintaining the rated
current for two periods of 1/2 seconds each, with a 15 second interval of zero current between the two periods .
Product to be tested . Contact Eaton for product rating
Magnum SBSE current limiting power circuit breaker with fast opening contacts .
Breaker applied in a tested fan cooled enclosure
Not released
1
4
4
4
6
1
3
4
5
6