MaGnuM PRoDuct GuiDe
CA013002EN—April 2017 www.eaton.com
38
Magnum IEC - Product specific information
Table 9 . Magnum IEC 60947-2 rated air circuit breakers continued
Frame
amperes
breaker
type
Frame
type
rms symmetrical current ratings ka
available
current
sensor
and
rating
plugs for
digitrip
rms trip
unit
(estab-
lishes
breaker
i
n
rating)
KeMa/
KeuR
ccc
Poles
avail-
able
inter-
rupting
@ 240
Vac
icu = ics
inter-
rupting
@ 440
Vac
icu = ics
inter-
rupting
@ 690
Vac
icu = ics
With-
stand
rating
icw
1-Sec @
440V/
690V
With-
stand
rating
icw
3-Sec
Fixed
internal
inst
trip
2500
MWI-625
Standard
65
65
65
65
n/a
200, 250,
300, 400,
630, 800,
1000, 1250,
1600, 2000,
2500
X
X
3 & 4
MWI-825
Standard
85
85
85
85
65
X
X
3 & 4
MWI-C25
Standard
100
100
85
85
65
85
3 & 4
MWI-H25
Standard
125
125
125
85
65
X
X
3 & 4
3200
MWK-232
Standard
85
85
85
85
65
3200
3 & 4
MWI-632
Standard
65
65
65
65
50
200, 250,
300, 400,
630
X
X
3 & 4
MWI-832
Standard
85
85
85
85
65
X
X
3 & 4
MWI-C32
Standard
100
100
85
85
65
85
X
X
3 & 4
MWI-H32
Standard
125
3 & 4
4000
MWI-64N
Double
65
65
65
65
n/a
2000,
2500,
3200,
4000
X
X
3 & 4
MWN-64N
Double
Narrow
66
66
66
66
n/a
X
X
3 & 4
MWI-641
Standard
66
66
66
66
n/a
X
X
3 & 4
MWI-84N
Double
85
85
85
85
n/a
X
X
3 & 4
MWN-84N
Double
Narrow
85
85
66
85/66
66
X
X
3 & 4
MWI-841
Standard
85
85
85
85
66
X
X
3 & 4
MWI-C4N
Double
100
100
100
100
n/a
X
X
3 & 4
MWN-C4N
Double
Narrow
105
105
66
105/66
66
X
X
3 & 4
MWI-C41
Standard
105
105
85
85
n/a
X
X
3 & 4
5000
MWI-85N
Double
85
85
85
85
n/a
2500,
3200,
4000, 5000
X
X
3 & 4
MWI-C5N
Double
100
100
100
100
n/a
X
X
3 & 4
6300
MWI-86N
Double
85
85
85
85
n/a
3200,
4000,
5000, 6300
X
X
3 & 4
MWI-C6N
Double
100
100
100
100
n/a
X
X
3 & 4
Interrupting ratings shown based on breaker equipped with integral digitrip rms trip unit . Interruption ratings for non-automatic breakers
are equal to the published withstand rating .
690V rating is not certified Kema/KEUR .
1100V Icu rating is 25kA .
1
1
2
3
3