EATON
Managed ePDU
t
User’s Guide
S
164201xxx Rev 1
DRAFT 10−OCT−2008
117
Chapter 12
Appendix D: Specifications
This appendix contains information describing the serial RJ−45 pinouts (Table 10) and
the serial RJ−11 (Table 11).
Table 10. RJ−45 PIN/Signal Definition
Pin No.
Signal
Direction
Description
1
DTR
Output
Reserved
2
GND
Signal Ground
3
+5V
Power for CIM
4
RX
Input
Receive Data (Data in)
5
TX
Output
Transmit Data (Data out)
6
N/C
N/C
No Connection
7
GND
Signal Ground
8
DCD
Input
Reserved
Table 11. RJ−11 PIN/Signal Definition
Pin No.
Signal
Direction
Description
1
+5V
Power
(500mA, fuse−protected)
2
GND
Signal Ground
3
RS485 (Data +)
bidirectional
Data Line +
4
RS485 (Data −)
bidirectional
Data Line −
5
GND
Signal Ground
6
1−wire