3.
Select the threshold from the second list under
Event
(see Figure 58). The list of
thresholds vary depending on what was selected in the first list.
Figure 58. Thresholds
4.
Select an direction from the
Event Direction
list.
S
If set to Assert, this alert will only trigger when a measured value moves past
a critical threshold (either above an upper critical threshold, or below a lower
critical one).
S
If set to Deassert, this alert will only trigger when a measured value returns to
normal from a critical state (either below an upper noncritical threshold, or
above a lower non]critical one).
S
If set to Assert & Deassert, this alert will trigger when a measured value
crosses any threshold state.
5.
Select a policy from the
Policy
list.
6.
Click
Add
. The alert is added to the system.
NOTE
No policies display in this drop−down list until you create them. See Creating Alert Policies" below
for instructions.
NOTE
If an Environmental Temperature or Humidity sensor is selected, an event will be created for each
logical Temperature or Humidity sensor. These event alerts can be deleted so that only the ones you want are
present.
Creating Alert Policies
Alert policies allow you to associate events with destinations. Policies determine
whether specific events trigger an entry in the event log, an email message to an
administrator, an SNMP trap, a selected outlet to be switched on/off/cycled, or any
combination of the four.
Summary of Contents for Managed ePDU
Page 1: ...Managed ePDU User s Guide...
Page 4: ......
Page 10: ...TABLE OF CONTENTS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 vi...
Page 16: ...SAFETY WARNINGS EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 6...
Page 20: ...RACK MOUNTING THE EPDU EATON Managed ePDUt User s Guide S 164201xxx Rev 1 DRAFT 10 OCT 2008 10...
Page 128: ......
Page 129: ...164201xxx1 164201xxx 1...