Page 11

SK-90610-Y4_EN

ENGLISH

4. Power cables connection

 

 This type of connection must be carried out by qualified electrical personnel.

 

Before carrying out any connection, check that the upstream protection device (Normal AC source)
is open "O" (Off).

 

 Before proceeding to connect the HotSwap MBP to the UPS, make sure the UPS has been properly shut 

down (refer to the UPS user manual).

Always connect the ground wire first.

4.1 MBP6K208

1.  Remove the L6-30P input power cable from the UPS I/O terminal blocks – refer to the UPS user manual for 

UPS I/O terminal blocks cover access.

2.  Connect the 2 power cables of I/O cord Set 

(1) 

to the UPS I/O terminal blocks, following color coding on 

the cables and the UPS I/O cover (blue for UPS Input / red for UPS Output) – refer to the UPS user manual 

to check the UPS terminal blocks connection.

 

3.  Connect the MBP detection cable from the I/O cord Set 

(1)

 to the specific UPS connector (MBP detect, 

refer to UPS User Manual). 

 Only with compatible EATON UPS, contact your Eaton reseller for more information.

4.  Slide the MBP I/O cover 

(2) 

after removing the 4 screws, to access to MBP terminal blocks.

5.  Punch the knockouts and insert the provided 

cable glands inside.

6.  Insert the L6-30P input power cable through the 

cable gland.

7.  Connect the wires to the Normal AC source (Input) 

terminal blocks.

8. Insert the Output cable through the cable gland.

9. Connect the wires to the Output terminal blocks.

10. Tighten the cable glands.

11. Slide back and secure the MBP I/O cover

 (2) 

with the 4 screws.

12. Connect the I/O cord Set

 (1)

 connector to the MBP, and secure it by fixing the 2 locking screws.

ion

1

2

Utility

Power

Load

to UPS output

RJ11 MBP detection

to UPS Normal

AC Source

OUTPUT

L1 L2

t

INPUT

L1 L2

t

2

OUTPUT

L1 L2

t

INPUT

L1 L2

t

Output cable

Normal AC Source

cable

2

1

1

Summary of Contents for MBP11K208

Page 1: ...NGLISH HotSwap MBP Maintenance Bypass MBP6K208 MBP11K208 Installation and user manual Copyright 2012 EATON All rights reserved Service and support Call your local service representative SK 90610 Y4_EN...

Page 2: ...found to comply with Class A UPS pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commer...

Page 3: ...ANSI NFPA 70 US installations only The upstream circuit breaker must be easily accessible The unit can be disconnected from AC power source by opening this circuit breaker and if still connected to U...

Page 4: ...cting the equipment 9 3 2 Unpacking the MBP 9 3 3 Checking the accessory kit 9 3 4 Mechanical Mounting 10 3 5 Installation requirements 10 4 Power cables connection 11 4 1 MBP6K208 11 4 2 MBP11K208 12...

Page 5: ...mprove waste treatment and facilitate recycling separate the various packing components p p The cardboard we use comprises over 50 of recycled cardboard p p Sacks and bags are made of polyethylene p p...

Page 6: ...onnector Hotswap MBP 5 6kVA range p p make before break feature to allow full servicing electrical power continuity when switching from UPS position to Bypass and vice versa p p Communication feature...

Page 7: ...entation MBP11K208 Tower installation Rack installation Wall mounting Description Weight lb kg Dimensions inch mm D x W x H MBP6K208 5 5 2 5 4 3 x 7 0 x 5 1 110 x 177 x 130 MBP11K208 13 7 6 2 8 7 x 13...

Page 8: ...ignal cable with RJ11 connector to plug to the UPS allows the communication to the UPS to manage the MBP status and the indication on UPS display panel of both following status p p MBP connection to U...

Page 9: ...free of humidity flammable gas and corrosion Packing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to...

Page 10: ...upstream the MBP Normal AC source 2 Recommended cable cross sections 3 Installation Terminal position Wire function Terminal wire size rating Minimum input wire size rating Tightening torque MBP6K208...

Page 11: ...terminal blocks connection 3 Connect the MBP detection cable from the I O cord Set 1 to the specific UPS connector MBP detect refer to UPS User Manual Only with compatible EATON UPS contact your Eaton...

Page 12: ...and secure it with 3 screws 9 Remove the I O terminal blocks cover of the UPS refer to the UPS user manual 10 Punch the Input and Output knockouts of the UPS I OTB cover and insert 2 provided conduit...

Page 13: ...C source Input terminal blocks of MBP 19 Insert the Output cable through the cable gland or a conduit through the conduit fitting 20 Connect the wires to the Output terminal blocks of MBP 21 Put back...

Page 14: ...now powered by the AC source 6 Set the Normal AC source switch of the MBP to the I position 7 Verify that the UPS is correctly powered UPS display panel illuminates 8 Press the UPS ON button to start...

Page 15: ...e 4 Switch the Normal AC source switch of the MBP to the 0 position and wait 30 seconds 5 UPS stops the UPS can now be disconnected as described below p p First disconnect the I O cord Set 1 from the...

Page 16: ...ted as described below p p First lock the Normal AC source switch 3 of the MBP to the 0 position the switch protection frame is able to fit a cable tie or a metallic locker 3 p p After opening the I O...

Page 17: ...ht of the MBP is still Off the load will be lost 8 Set the MBP manual Bypass switch to the UPS position the Bypass mode red light of the MBP goes Off indicating that the load is now powered by the UPS...

Page 18: ...2011 ESD IEC 61000 4 2 level 3 Radiated field IEC 61000 4 3 level 3 EFT IEC 61000 4 4 level 4 Fast transients IEC 61000 4 5 level 4 Electromagnetic field IEC 61000 4 6 level 3 Conducted magnetic field...

Reviews: