Unit installation
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
2.4 Installation space
Indoor unit:
The rack air conditioner indoor unit is installed at the bottom of the IT equipment cabinet so when installing the
IT equipment cabinet, do ensure that there is enough space around the installation location to prepare for the
operation and maintenance of the air conditioner indoor unit.
The recommended installation space dimensions for server cabinets with rack air conditioner are shown in the
following figure: 2.2.
Figure 2.2
Outdoor unit:
The installation space requirements for outdoor units are shown in the following
The distance from the
wall is greater than
300mm.
The distance from
the wall is greater
than 500mm.
The distance
from the wall
is greater than
300mm.
Figure 2.3