10
Unit installation
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
Tool names
Schematic diagrams
Specifications
Usage
Pressure gauge
Low voltage test range:
-0.1~3.6 MPa (- 30~550 Psi).
High voltage test range:
-0.1~5.5 Mpa (- 30~800Psi).
Accuracy level: 1.6
It is used to check the pressure of the
system and judge whether the system is
normal or not.
Refrigerant hose
R410A specification, ≥ 2. Wall
thickness, ≥ 12mm. Impervious grade,
RMA-A
Vacuum, replenish / charge refrigerant.
Check system pressure
Refrigerant
DuPont SUVA R410A is recommended Charge / replenish refrigerant
Electronic weighing
Resolution, ≤ 5g.
Accuracy, ± 5%.
Built-in solenoid valve, automatic
quantitative injection
Charge / replenish cold refrigerant
weighing
Vacuum pump
R410A special vacuum pump with
solenoid check valve. Absolute
pressure of 12Pa
Vacuumizing for installation / maintenance
system
Inner hexagonal
spanner
5mm
(
5#
)
Open / close globe valve
Cutter
Suitable pipe diameter, 4~28mm
Copper tube cutting
Used for cutting copper tubes
Scraper
——
Polished the machined surface of copper
tubes