29
Unit operation
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
3.5 Unit shutdown
The shutdown of the unit should be in accordance with the prescribed procedures, and do not start and stop
frequently. Steps 1 and 2 are carried out automatically after pressing the “ ” key on the main page of the
manipulator to enter the shutdown state, and the status of the unit on the interface changes from “running” to
“shutdown”.
1. Stop the refrigeration system.
2. Stop the indoor fan.
3. Turn off the power supply.
3.6 Daily operation inspection of unit
During daily operation, observe closely the following points:
1. Whether the temperature, sound and vibration of the running equipment normal, otherwise take the
neccessary steps to address them. Check whether the current and surface temperature of the running
equipment is normal.
2. Whether the outdoor ambient temperature is within the required range, otherwise it will be adjusted.
3. After the operation of the unit is stable, check whether the suction pressure and exhaust pressure are normal,
otherwise it should be adjusted.
4. Check whether the temperature and humidity in the room are within the normal range.
3.7 Test record and form
Reference range
Actual record
Reference range
Actual record
Indoor unit model See nameplate
Outdoor unit
model
See nameplate
Indoor unit
number
See nameplate
Outdoor unit
number
See nameplate
SN code
See the rear of the unit
SN code
See below the nameplate
Indoor ambient
temperature
during test run
General 24
°
c ~ 30
°
c
Total current of
outdoor unit
Less than the maximum current of the
nameplate
Indoor ambient
humidity during
test run
Generally 40% ~ 60%
condenser inlet
air temperature
That is, the outdoor ambient
temperature is not higher than 45
°C
.
Power supply
voltage
220 V ± 15%
condenser outlet
air temperature
It is generally 8-12
°C
higher than the
inlet air temperature.
Total current of
indoor unit
Less than the maximum current of
the nameplate
condensing
pressure
General 23.5~30 bar (affected by the
environment)
Running time
/
System high
voltage
General 23.5~30 bar (affected by the
environment)
Indoor air
intake dry bulb
temperature
Generally 25
°
c 35
°
c (default 35
°
c)
System low
pressure
General 8.9~11bar (affected by load)
Indoor air inlet
humidity
Generally 40% ~ 60% (default 50%)
suction
temperature
Generally 12 ~ 24
°C
(affected by load)
Air outlet dry
bulb temperature
of indoor unit
It is generally 8 ~ 12
°
c lower than
the inlet air temperature (affected
by load)
Discharge
temperature
General 70 ~ 80
°C
(affected by
environment)
Remarks Generally, when the indoor unit is fully loaded, the air temperature difference in and out of the indoor unit is about 12
°C
.
Experimenter:____________________
Trial time:________________________