MEMSHIELD 4 INSTALLATION INSTRUCTIONS FOR 800A PANELBOARDS / PAN ASSEMBLIES
EM4PB680, EM4PB1280, EM4PB1680
EM4PBP680, EM4PBP1280, EM4PBP1680
Instruction Leaflet LT1223 (02/19)
800A Incoming MCCB
EM4PBK804
Transit
mount
discard
Remove
for access
Fit
Incoming
Mount
Incoming Modules
3 Pole & Neutral - Bottom Entry
Form 4 Type 6 Group Mounted
Secure
all
shields
800A Incoming Direct Cable
EM4PBK804L
MCCB Incoming Cover
Knockout Removal
Do not remove for direct cable
incomer
Remove for Bottom Entry 3 pole and N
Remove for Bottom Entry 4 pole
Panelboards are supplied as Bottom Entry and Form 4 Type 6 Group Mounted without modification
General Note:
When fixing M5 thread forming
screws tightening torque is 3.8 Nm
4 Pole -Bottom Entry
Form 4 Type 6
Secure
all
shields
IMPORTANT NOTES
1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician in
accordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring Regulations
BS7671), Construction (Design and Management) Regulations, HSG150
–
Health and Safety in Construction, Statutory requirements
and any Specific instruction issued by the Company.
2. After completing the installation and testing of this product it is essential that this leaflet is drawn to the attention of the person
responsible for its future operation and maintenance, and is at all times available for ready reference.
3. The notes assume throughout that the product is disconnected from the supply. It is essential that this is done before any work is
carried out.
4. These Panelboards are only designed for use with EATON MCCBs. Failure to comply will result in invalid warranty and certification.
Bottom
Entry
800A Incoming Neutral
EM4PBNK80
4 Pole - Bottom Entry
Form 4 Type 6 Group Mounted
Secure
all
shields
30Nm
Transit
mount
discard
Remove
for access
Fit
Mount
46Nm
30Nm
30Nm
Fit
Interphase
shields
46Nm
Fit shield
Fit neutral