1.6 MGR10C technical specifications
1.6.1 Measurement Accuracy
Range Max.
Current Resolution
Accuracy at full rated current
Temp. Coefficient
30 k
10
A 1
±
(0.05%Rdg+0.02%FS)
50 ppm
3 k
0,1mA
100m
±
(0.05%Rdg+0.01%FS)
50 ppm
300
1mA
10m
±
(0.05%Rdg+0.01%FS)
50 ppm
30
10mA
1m
±
(0.05%Rdg+0.01%FS)
50 ppm
3
10mA
100
±
(0.05%Rdg+0.01%FS)
50 ppm
200m
Not available
30m
Not available
3m
Not available
The accuracy is quoted at full rated current and the display count is 30,000 plus sign and unit.
FS = Full Scale
1.6.2 Programmable current
The measurement current is not adjustable on each resistance range
Range
Max Current
Min Current
Steps
30 k
10
A 10
A
Not available
3 k
100
A 100
A
Not available
300
1mA 1mA
Not
available
30
10mA 10mA
Not
available
3
10mA 10mA
Not
available
200m
Not available
30m
Not available
3m
Not available
The accuracy of the current is
±
1% .
Open circuit voltage is 2 V +/-5% .