Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01
33..44
M
Moovviinngg aanndd P
Pllaacciinngg tthhee M
Miinnii P
PD
DU
U
Move the Mini PDU off its pallet with a forklift as follows:
1.
The Mini PDU is attached to its pallet by its seismic brace with wood screws. With the pallet resting on the
floor, remove the wood screws.
2.
Insert forklift or palette jack forks under the Mini PDU cabinet on long side of the unit.
Be careful not to damage the casters or the seismic brace.
3.
Move the unit to its installation location next to server racks and withdraw the forklift. Unit has casters and
can be precisely rolled into position. Seismic brace must face opposite the server rack.
4.
Adjust leveling feet to stabilize the unit using an open wrench.
5.
Secure seismic brace to floor. Installer chooses and provides attachment hardware.
Figure 2. Seismic Brace
This image is extracted from the
6,
30 kVA Mini PDU Drawings
33..55
A
Attttaacchhiinngg tthhee C
Caabbllee LLaaddddeerr
The Mini PDU has a top-mounted Cable Ladder Bracket next to the Cable Entry Brush Panel for attaching the
Cable Ladder.
The Bracket can be attached on the left or right side of the Mini PDU, allowing the Cable Ladder to be
positioned on either side.
The Bracket should be installed on the server rack side of the Mini PDU.