Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
31/55
Description du Status
Status to 0
Status to 1
Word
(hex)
Bit
Module 5
General alarm
Absent
Present
65
0
Fan failure
Absent
Present
65
1
Internal communication fault
Absent
Present
65
2
Inverter thermal overload
Absent
Present
65
3
Inverter fault
Absent
Present
65
4
Inverter fuse blown
Absent
Present
65
5
Load short circuit
Absent
Present
65
6
Module 6
General alarm
Absent
Present
66
0
Fan failure
Absent
Present
66
1
Internal communication fault
Absent
Present
66
2
Inverter thermal overload
Absent
Present
66
3
Inverter fault
Absent
Present
66
4
Inverter fuse blown
Absent
Present
66
5
Load short circuit
Absent
Present
66
6
Module 7
General alarm
Absent
Present
67
0
Fan failure
Absent
Present
67
1
Internal communication fault
Absent
Present
67
2
Inverter thermal overload
Absent
Present
67
3
Inverter fault
Absent
Present
67
4
Inverter fuse blown
Absent
Present
67
5
Load short circuit
Absent
Present
67
6
Module 8
General alarm
Absent
Present
68
0
Fan failure
Absent
Present
68
1
Internal communication fault
Absent
Present
68
2
Inverter thermal overload
Absent
Present
68
3
Inverter fault
Absent
Present
68
4
Inverter fuse blown
Absent
Present
68
5
Load short circuit
Absent
Present
68
6