Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
53/55
6.12.3 Read of the personalization table
Description
Word (hex)
Unit
High threshold temperature (°C)
32C
0
Low threshold temperature (°C)
32D
0
Temperature hysteresis (°C)
32E
0
Offset temperature (deci °C)
32F
0
High threshold humidity (%)
330
0
Low threshold humidity (%)
331
0
Humidity hysteresis (%)
332
0
Humidity offset
(‰)
333
0
Inputs call mask
– input 1 close notification
334
0
Inputs call mask
– input 1 open notification
334
1
Inputs call mask
– input 2 close notification
334
2
Inputs call mask
– input 2 open notification
334
3
Inputs call mask
– high temperature notification
334
4
Inputs call mask
– low temperature notification
334
5
Inputs call mask
– high temperature shutdown
334
6
Inputs call mask
– low temperature shutdown
334
7
Inputs call mask
– high humidity notification
334
8
Inputs call mask
– low humidity notification
334
9
Inputs call mask
– high humidity shutdown
334
A
Inputs call mask
– low humidity shutdown
334
B
Inputs call mask
– input 1 close shutdown
334
C
Inputs call mask
– input 1 open shutdown
334
D
Inputs call mask
– input 2 close shutdown
334
E
Inputs call mask
– input 2 open shutdown
334
F
Input 1 identification
336 - 343
Input 2 identification
344 - 351