Page 13
614-09354-01_EN
ENGLISH
3. Installation
3.8 Installation requirements
Recommended protective devices and cable cross-sections
3.8.3 9PXMEZ11Ki use with 9PX8000 or 9PX11000 UPS
•
Separate input source recommended protective devices
For Parallel Operation
D curve, 125A if use with 9PX11000 UPS
D curve, 100A if use with 9PX8000 UPS
For Redundancy Only
D curve, 63A if use with 9PX11000 UPS
D curve, 50A if use with 9PX8000 UPS
2 poles circuit breaker
2 poles circuit breaker
•
Recommended cable cross-sections:
9PXMEZ11Ki
Normal AC source and Bypass AC source
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input
wire size rating
Breaker
D Curve
Parallel
Operation
with 9PX11000
UPS
L1
Phase
4-35 mm
2
(12-4 AWG)
35 mm
2
(1 AWG)
125A
N
(L2)
Neutral
(Phase)
Ground
Parallel
Operation
with 9PX8000
UPS
L1
Phase
4-35 mm
2
(12-4 AWG)
25 mm
2
(2 AWG)
100A
N
(L2)
Neutral
(Phase)
Ground
Redundancy
Only
with 9PX11000
UPS
L1
Phase
4-35 mm
2
(12-4 AWG)
10 mm
2
(8 AWG)
63A
N
(L2)
Neutral
(Phase)
Ground
Redundancy
Only
with 9PX8000
UPS
L1
Phase
4-35 mm
2
(12-4 AWG)
10 mm
2
(8 AWG)
50A
N
(L2)
Neutral
(Phase)
Ground
Summary of Contents for ModularEasy 9PXMEZ11Ki
Page 1: ...9PXMEZ6Ki 9PXMEZ11Ki Installation and user manual English Fran ais Deutsch Espa ol...
Page 2: ......
Page 99: ...ModularEasy 9PXMEZ6Ki 9PXMEZ11Ki Copyright 2014 EATON 614 09354 01_RU...
Page 101: ...3 614 09354 01_RU ModularEasy 15 C 60 C ModularEasy EATON Eaton ModularEasy...
Page 106: ...8 614 09354 01_RU 2 2 3 UPS NMC Ready Eaton 2 4 1 2 Power 1 2 3 1 1 2 0 1 0 2 5 Enter...
Page 108: ...10 614 09354 01_RU 3 3 4 3 5 9RK...
Page 109: ...11 614 09354 01_RU 3 3 6 19 EBM 9PX EBM 240V 3 7 Trollet Frame BINTSYS 9PXMEZ11Ki 9PXMEZ6Ki...
Page 113: ...15 614 09354 01_RU 4 10 1 ModularEasy 11 9PX...
Page 123: ......
Page 124: ...www eaton com Powerquality EATON 9PX_ModularEasy 614 09354 01...