Choose the communication port where the cable between the PC and the
SmartWire-DT gateway is connected. If using the EU4A-RJ45-USB-CAB1 cable,
choose the virtual comm port the USB port has been mapped to. Click the Online
button. Under Target Configuration click the
Renew
button. This triggers the
SmartWire-DT Ethernet gateway to read and store the list of devices physically
present in the SmartWire-DT system. Also under Target Configuration, click the
Device to PC
button. This will upload the SmartWire-DT system configuration
from the gateway to the PC.
Under the View drop down menu select Communication View to toggle back to
the offline project which is the project we just uploaded from the gateway. Make
the following changes/additions:
1. Click on each contactor (DIL-SWD-32-002) one at a time and select the
Device Parameters tab in the section at the bottom of the screen.
2. Select the following contactor type for each contactor: DIL-SWD-32-002
with contactor XTCE 7-9, XTRE per the list of SmartWire-DT part numbers
shown earlier in this document.
3. Add the following flat to round cable adapter between the M22-SWD-
K22LED-G and the M22-I3 enclosure: SWD4-8FRF-10. Note that when
the software allows you to drop the device onto the network is when the
blue vertical bar appears. This adapter part number is located under
Network Accessories/Adapter on the left portion of the screen.
4. Click the Ethernet gateway to select it and display its parameters at the
bottom portion of the screen. Then click the Device Parameters screen to
select the mode, EtherNet/IP or Modbus TCP.
5. Click the Ethernet Parameters tab and enter the IP address, Subnet Mask
and Gateway Address for the gateway.
6. Save the project then select Communication View under the View drop
down menu to toggle back to the Communication screen.
7. Click the Online button then select the
PC to Device
button under the
Planned Configuration to download the modified project to the gateway.
The SmartWire-DT system is now ready to be controlled and monitored with an
EtherNet/IP or Modbus TCP Ethernet master. Please refer to the EtherNet/IP or
Modbus TCP section below for additional information on configuring the network
master to control and monitor the devices on the SmartWire-DT system.