Installation
20
05/08 AWB2528-1611en
Removing the communication module
Use a screwdriver with a 100 x 3.5 mm slot width.
X
Insert the screwdriver into the lug of the fixing shaft
catch.
X
Lever out the slide catch.
X
Pull out the communication module from the fixing shafts
.
Figure 18: Releasing the fixing shaft
Connections
Terminals
The MFD-CP4-CO is fitted with cage clamp terminals for
connecting the power supply and the connection cable to the
CANopen interface.
Tool for cage clamp terminals
Slot-head screwdriver, width 3.5 mm x 0.6 mm.
Connection cross-sections of the MFD cage clamp
terminal cables
• Power supply terminal: 0.08 - 2.5 mm
2
(AWG 28 - 12)
• Interface terminal
0.14 to 0.5 mm
2
(AWG 26 – 20)
1
2
3
1
3
2