Control Circuit Devices M22-
SWD…
100
06/09 AWB2723-1613en
M22-SWD-K11LEDC-(W/B/G/R)
The function element has one input byte and one output byte
at its disposal.
Inputs
Byte 0:
NO1
NC1
7
6
5
4
3
2
1
0
-
P
-
F
-
-
NC1
NC1
Bit
Designation
Meaning
0
NC1 = Normally Close
0: Contact actuated
1: Contact not actuated
1
NO = Normally Open
0: Contact not actuated
1: Contact actuated
2
not used
-
3
not used
-
4
F = Failure
0: No diagnostic alarm
1: Diagnostics available
5
not used
-
6
P = Module present
0: Module not available
1: Module available
7
not used
-