Technical data
113
06/09 AWB2723-1613en
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables
kV
2
2
2
Signal cables
kV
1
1
1
SmartWire-Darwin cables
kV
1
1
1
Surge (IEC/EN 61131-2:2008, Level 1)
–
Supply cables 0.5
kV
–
Radiated RFI (IEC/EN 61131-
2:2008, Level 3)
V
10
10
10
Ambient climatic conditions
Operating ambient temperature
(IEC 60068-2)
°C
–25 … +55
–25 … +55
–25 … +55
Condensation
prevent with suitable measures
Storage
°C
–40…70
–40…70
–40…70
Relative humidity, non-
condensing (IEC/EN 60068-2-
30)
%
5 … 95
5 … 95
5 … 95
SmartWire-Darwin interface
Station type
SmartWire-Darwin station (slave)
Baud rate setting
automatic
SmartWire-Darwin status
LED
Green
Connection
Plug, 8-pole
Connection plug: external device plug SWD4-8SF2-5
Current consumption (15 V SWD supply)
Connection supply and I/O
Connection type
Push-In
solid
mm
2
0.2 - 1.5 (AWG 24 - 16)
flexible with ferrule
1)
mm
2
0.25 - 1.5
0.25 - 1.5
0.25 - 1.5
24 V DC supply for output supply
Rated operational
voltage
U
e
V
–
24 DC -15 % /
+20 %
–
Input voltage ripple
%
–
5
–
Protection against polarity reversal
–
Yes
–
EU5E-SWD-
8DX
EU5E-SWD-
4D4D
EU5E-SWD-
4D2R
Summary of Contents for Moeller SmartWire-Darwin Series