Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
42
06/09 AWB2723-1613en
The terminals on the SmartWire-Darwin module for DILM are
suitable for cables AWG24 to AWG16 and flexible cables
with a cross-section of 0.25 mm
2
to 1.5 mm
2
.
When using ferrules it has to be ensured that the ferrule
length is at least 8 mm.
The following jumpers can be used for wiring reversing
starters.
h
Caution!
The connection cables to the potential-free auxiliary
contacts at connection X0-X1-X2
g
for the potential-free
contacts and at connection X3-X4
h
for the auxiliary
contact enable may have a maximum length of 2.8 m.
h
Caution!
The wiring sets DILM12-XRL and PKZM0-XRM12 must not
be used for the assembly of the reversing starters.
The A2 connection of the contactors must not be bridged.