Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
60
06/09 AWB2723-1613en
DIL-SWD-32-002
The function element has one input byte and one output byte
at its disposal.
Inputs
Byte 0:
7
6
5
4
3
2
1
0
-
P
-
F
M
I1
(X1-
X0)
I0
(X1-
X2)
C
Bit
Designation
Meaning
0
C = Contactor
0: Contactor not tripped
1: Contactor tripped
1
I0 (X1-X2)
0: Auxiliary contact for X1-X2 opened
1: Auxiliary contact for X1-X2 closed
The meaning depends on the auxiliary contact used.
2
I1 (X1-X0)
0: Auxiliary contact for X1-X0 opened
1: Auxiliary contact for X1-X0 closed
The meaning depends on the auxiliary contact used.
3
M = Manual
0: Automatic
1: Manual mode
4
F = Failure
0: No diagnostic alarm
5
not used
-
6
P = Module present
0: Module not available
1: Module available
7
not used
-