Engineering
83
06/09 AWB2723-1613en
Engineering
The SmartWire-Darwin base function elements replace the
previous M22-KC10 / KC01 contact elements and the
corresponding M22 LEDC... elements. They are used in the
surface mounting enclosures M22-I1 to M22-I6 in
connection with the corresponding M22-SWD-ILP1-6 PCBs.
Up to six operator control and indicator light functions can
be realized with them. The printed circuit boards create the
connection with the SmartWire-Darwin network. The known
M22 front elements for the control circuit function are used
on the front.
The surface mounting enclosures are connected to the
SmartWire-Darwin network via the SmartWire-Darwin round
cable SWD4-50LR8-24.
The round cable can be connected directly by means of
VM20 (metric cable gland) or plugged in. 8-pole enclosure
bushings as plug/socket versions are used for the plug-in
version.
Connection of the round cable to the cable gland
Figure 28: Connection with a cable gland
1
3
2
2
IN
V-M20