Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
52
06/09 AWB2723-1613en
Application for EN ISO13849-1 and EN 62061
The SmartWire-Darwin system is suitable in applications up
to safety category 3, PL d in accordance with EN ISO 13849-
1 and SIL Cl2 in accordance with EN 62061.
Applications in North America
For applications for the North American market special care
must be taken with the approval of the individual
components of the system SmartWire-Darwin.
Current carrying capacity of the SmartWire-Darwin
connecting cable in accordance with NFPA 79
If the SmartWire-Darwin connection system is used for
applications in North America, the maximum current
carrying capacity of the SmartWire-Darwin connecting cable
is reduced from 3 A to 2 A.
If, due to the application, the maximum current carrying
capacity of the SmartWire-Darwin connecting cable exceeds
the value 2 A, this can be compensated by means of
additional SmartWire Darwin power feeder modules
(
chapter "Power Module EU5C-SWD-PF1-1, EU5C-
j
Danger!
The total assembly of the safety relevant controls must
correspond to the required safety category.