11
INM MTL831C Rev 7
• Extreme noise source is affecting the data highway cable. This could
include VFDs, welders, etc.
• Check all wiring terminations to see that they are tight and there are no
unintended shorts.
• Verify that the data highway shield is earthed at one location only.
• Verify the integrity of the data highway cable.
• Use the PC software to check the diagnostic information.
• Try rebooting each device connected to the data highway one at a time.
• Contact Eaton for assistance if the source of the issue cannot be found.
The POWER and ERROR lights alternately turn on and off
• This is an indication that the unit is being updated with new firmware. If
a firmware update fails to complete properly, the unit can get stuck in this
mode. Perform the firmware update again. If this does not fix the issue,
contact Eaton for assistance.