34008030EN/AD - Page 30
6. Life Cycle Monitoring (LCM)
6.1 Description
This function, embedded in the UPS, displays messages, on screen and communication channels, at every important
stage of the UPS’s life, allowing you to:
Secure your installation power continuity
Anticipate maintenance actions thanks to automatically displayed warnings while displaying automatic warnings
when maintenance actions need to be planned :
Reset or disable LCM
Press the "Enter" button
(27)
to display
LCM warning details.
LCM warning details
Signification
BATTERY CHECK RECOMMENDED
CONTACT EATON AT
www.eaton.com
Battery is approaching its reliability end of life. Risk to reduce
dramatically backup time
In case of any LCM messages displayed:
◗
For temporary reset: press the escape button
(24)
more than 3 seconds, into Status and Alarm screen
,
to cancel
temporary the alarm status.
The alert will be repeated twice each 30 days.
◗
For permanent reset: press the enter button
(27)
more than 3 seconds, into LCM warning screen, to cancel
permanently this LCM event.
At any time:
To Disable all LCM messages select "disable all" ,into LCM menu with LCD navigation.
Be careful: you will not be aware of any LCM events that can happen on the UPS if you disable all LCM messages.
ESC
I
O
LOAD PROTECTED
x.xkVA / xxx% LOADED
LCM WARNING
SINGLE UPS
27