Instruction Leaflet 

IL29C109J

Effective  November 2013

Installation Instructions for ND, HND, NDC, CND,

CHND, CNDC Circuit Breakers with Digitrip OPTIM

Trip Unit and Powernet, and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

CONTACT WITH ENERGIZED EQUIPMENT CAN 

RESULT IN DEATH, SEVERE PERSONAL INJURY, 

OR SUBSTANTIAL PROPERTY DAMAGE.  DO NOT 

NANCE ON EQUIPMENT WHILE IT IS ENERGIZED.

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT

BEFORE PROCEEDING WITH THE TASK, AND 

TY PROCEDURES.

ATTEMPT TO INSTALL OR PERFORM MAINTE-

ALWAYS FOLLOW GENERALLY ACCEPTED SAFE-

EATON IS NOT LIABLE FOR THE MISAPPLICATION

MISINSTALLATION OF ITS PRODUCTS.

The user is cautioned to observe all recommendations, 

warnings and cautions relating to the safety of person-

nel and equipment as well as general and local health 

and safety laws, codes and procedures. 

The recommendations and information contained herein 

are based on Eaton experience and judgment, but should

not be considered to be all-inclusive or covering every

application or circumstance which may arise. If any que- 

stions arise, contact Eaton for further information or  

instructions. 

Figure 1-1 N-Frame OPTIM Series C Circuit Breaker

Frame(OPTIM 750, 1050 shown, the Model

550 has no Side Bracket) 

1.0

INTRODUCTION

General Information 

The N-frame OPTIM Series C circuit breaker (Figure 

1-1)

types ND, HND, and NDC are 600 VAC maximum

rated devices with Digitrip OPTIM Models 550, 750 or 

1050 trip units rated 800A or 1200A maximum continu-

ous current. They are for AC applications only and can

be reverse fed. They are listed in accordance with 

Underwriters Laboratories, Inc. Standard UL 489 and

satisfy the requirements of International Electrotechnical 

Commission Recommendations No. IEC 947-2.  OPTIM

750 and 1050 N-Frame circuit breakers are equipped 

with zone interlocking and an auxiliary switch and alarm

(signal)/lockout switch for customer usage. Other inter-

nal accessories are available but must be factory 

installed since they are factory sealed. Model 550 is not 

sealed and can accommodate field installed acces-

sories, including an IMPACC communications kit. 

Contact Eaton for the following information and user manuals: 

N-Frame and Accessories Selection Data  29-120N

Instructions and Overview of OPTIM 

Trip Units 

Instructions on the Operation of Digitrip 

OPTIMIZER Hand Held Programmer 

Instructions on the Operation of Digitrip 

Breaker Interface Module 

Instructions on the Operation of Digitrip 

OPTIM Trip Units 

Digitrip OPTIM Wiring Diagrams 

9

2

a

t

a

D

n

o

it

a

c

il

p

p

A

-167N

100 Percent Rated N-frame Circuit Breakers

CND, CHND, and CNDC circuit breakers are suitable for 

continuous operation at 100 percent of the frame rating 

in an enclosure which measures at least 42” height, 

22.75” width and 11.5” depth. The 800A version 

requires no ventilation. The 1200A version requires 224 

sq. in. of ventilation on the front face of the enclosure

(72 sq. in. top, 72 sq. in. bottom, 40 sq. in. left and 40

sq. in. right). The 1200A version has to be used with the

supplied conductor extensions and terminal barriers as

shown in Figure 2-2. Use only 90°C rated wire with 

ampacity based on 75°C rated conductors. Use Copper 

only or 

terminals only. 

!

WARNING

Summary of Contents for ND Series

Page 1: ...t IL29C109J Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock Contents Description Page 1 0 Introduction 2 2 0 In...

Page 2: ...for AC applications only and can be reverse fed They are listed in accordance with Underwriters Laboratories Inc Standard UL 489 and satisfy the requirements of International Electrotechnical Commiss...

Page 3: ...ment configuration the cir cuit breaker can be mounted using different styles of hardware The following steps describe how to mount the circuit breaker using standard hardware When special hardware is...

Page 4: ...t Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www eaton com Figure 2 2 Conductor Extensionsand Terminal Installation for 100 Rating 0 31 8 0 31 8 25 Tap...

Page 5: ...le and the PUSH TO TRIP but ton in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised letteringto indicate ON and OFF On the handle ON OFF and...

Page 6: ...Bell Alarm Auxiliary Switch is only available on the OPTIM 1050 units If damaged a terminal block cover can be purchased through Eaton The part number is 4214844699 NOTICE 1 It is crucial to connect t...

Page 7: ...roblem Red On White Trip Color Green Off I On Figure 3 1 CircuitBreaker Switch circuit breaker to ON and OFF several times to be sure that the mechanism linkages operate freely and do not bind If mech...

Page 8: ...es that certain minimum instructions GROUND FAULT TEST RECORD FORM round Fault Test Records should be Retained by Those in Charge of the Building s lectrical Installation in order to be available to t...

Page 9: ...rough the neutral sensor as shown in Figure 4 3 The breaker should not trip and the alarm indicator if supplied should not operate Repeat the test on the other two phases Source L Low Load Current Lim...

Page 10: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 11: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 12: ...further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropr...

Reviews: