Instruction Leaflet 

IL29C109J

Effective  November 2013

Installation Instructions for ND, HND, NDC, CND,

CHND, CNDC Circuit Breakers with Digitrip OPTIM

Trip Unit and Powernet, and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

2 50 R

(6 35 R)

1 $06

(48 41)

Handle

188 R

5 587 

(141 91) 

(80 95)

6 375

(161 92) 

FRONT COVER CUTOUT 

Figure 2-4 Circuit Breaker Escutcheon Dimensions 

HAZARDOUS VOLTAGE CONDITIONS CAN CAUSE 

DEATH OR SEVERE PERSONAL INJURY. MAINTAIN 

AGE SPACINGS AT TERMINATIONS.

ORIGINAL ELECTRICAL CLEARANCE AND CREEP-

Connect the control wires and power wires to their 

appropriate locations on the male plug of the terminal

block, see Figure 2-6. Control power is necessary if 

IMPACC communication is required.

Install an appropriate rating plug, see Table 

2.1.

2-10.

Plug in the hand held Digitrip OPTIMIZER into the 

programming port and set the INCOM address. Then 

set the various trip unit current settings using the OPTI-

MIZER, or use the Breaker Interface Module when 

INCOM is available.  If IMPACC Series software is 

part of the system, this too can be used to set the trip

unit settings.  Refer to the user manuals for details. 

3.0

MANUAL OPERATION 

Manual operation of the circuit breaker is controlled by 

the circuit breaker handle and the PUSH-TO-TRIP but-

ton in the trip unit. The circuit breaker handle has three

positions, two of which are shown on the cover with 

raised lettering to indicate ON and OFF. On the handle,

ON, OFF, and trip are also shown by a color-coded strip 

for each circuit breaker handle position: red for ON, 

white for tripped, and green for OFF (see Figure 

3-1).

Breaker

Figure 2-5

Securement of Cable (See caution note for

bracing instruction) 

Circuit Breaker Reset 

After a trip operation, the circuit breaker is reset by mov-

ing the handle to the Reset (extreme OFF) position. It is

not necessary to press the reset button before resetting 

the breaker. The reset button affects only the cause of 

trip indicator 

and trip information in the trip’s

memory. It does not affect the operation of the circuit

breaker itself. 

No circuit breaker should be

until the

cause

of trip is known and the situation rectified. 

PUSH-TO-TRIP Button 

The PUSH-TO-TRIP button operates the circuit breaker 

tripping function and may be used to periodically exer-

cise the operating mechanism. The button is designed

to be operated by a small screwdriver. 

4.0

INSPECTION AND FIELD TESTING 

Series C molded case circuit breakers are designed to

provide years of almost maintenance-free operation. The 

following procedure describes how to do a limited

amount of field inspection and testing of a circuit breaker. 

Inspection

Circuit breakers in service should be inspected 

!

WARNING

Summary of Contents for ND Series

Page 1: ...t IL29C109J Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock Contents Description Page 1 0 Introduction 2 2 0 In...

Page 2: ...for AC applications only and can be reverse fed They are listed in accordance with Underwriters Laboratories Inc Standard UL 489 and satisfy the requirements of International Electrotechnical Commiss...

Page 3: ...ment configuration the cir cuit breaker can be mounted using different styles of hardware The following steps describe how to mount the circuit breaker using standard hardware When special hardware is...

Page 4: ...t Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www eaton com Figure 2 2 Conductor Extensionsand Terminal Installation for 100 Rating 0 31 8 0 31 8 25 Tap...

Page 5: ...le and the PUSH TO TRIP but ton in the trip unit The circuit breaker handle has three positions two of which are shown on the cover with raised letteringto indicate ON and OFF On the handle ON OFF and...

Page 6: ...Bell Alarm Auxiliary Switch is only available on the OPTIM 1050 units If damaged a terminal block cover can be purchased through Eaton The part number is 4214844699 NOTICE 1 It is crucial to connect t...

Page 7: ...roblem Red On White Trip Color Green Off I On Figure 3 1 CircuitBreaker Switch circuit breaker to ON and OFF several times to be sure that the mechanism linkages operate freely and do not bind If mech...

Page 8: ...es that certain minimum instructions GROUND FAULT TEST RECORD FORM round Fault Test Records should be Retained by Those in Charge of the Building s lectrical Installation in order to be available to t...

Page 9: ...rough the neutral sensor as shown in Figure 4 3 The breaker should not trip and the alarm indicator if supplied should not operate Repeat the test on the other two phases Source L Low Load Current Lim...

Page 10: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 11: ...eaflet IL29C109J Effective November 2013 Installation Instructions for ND HND NDC CND CHND CNDC Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www...

Page 12: ...further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropr...

Reviews: