background image

3

Instruction Booklet 

IB157001EN

Effective May 2015

Fixed capacitor banks (Unipump, Unipak, and Unipak 

detuned filter) low voltage (600 V and below), NEMA 1 

NEMA 3R (outdoor) enclosed versions 

EATON

 www.eaton.com

Receiving

Check the capacitor bank when receiving to verify that there is no 

shipment or handling damage during transit . Minor damage such as 

scratches or small dents to the outer enclosure will not inhibit the 

capacitor’s performance, but units with large dents or leaks should 

not be installed . In case of major damage, file a claim against the 

carrier and also notify the nearest Eaton sales office for instructions 

regarding the disposition of the capacitor bank .
Check the capacitor’s nameplate to verify that the nameplate voltage 

rating matches the system and the applied voltage . 

Installation

Install capacitor bank in accordance with all applicable local electrical 

standards (NEC

T

 NFPA 70, etc .) . Failure to properly install capacitor 

bank in accordance with local electrical safety standards may cause 

electrical shock, fire, and incorrect operation including reduction in 

useful life of the capacitor bank .

Preparation for installation

The capacitor bank storage temperature range is –40 °C to +55 °C, 

and the operating temperature range is –40 °C to +46 °C . For 

optimal equipment life, prepare to install the capacitor bank in an 

area free of external heat sources, such as direct sunlight .
For optimal equipment life, a harmonic resonance evaluation 

should be performed prior to installation, particularly if an unfiltered 

capacitor bank is used .

Installation locations

Capacitor banks should be located in a well-ventilated area with a 

minimum of 3 inches of clearance around all sides and top of the 

enclosure to ensure good air circulation .  
Equipment rated for indoor use should be installed indoors in a dry 

environment . Outdoor rated units shall be shielded from the radiant 

heat of direct sunlight by a canopy or a sunshade . 
Both for indoor and outdoor installations, the maximum ambient 

temperature should not exceed 40 °C (104 °F) and the annual average 

temperature should not exceed 35 °C (95 °F) . Higher location ambient 

temperatures will cause capacitor failure and reduction in useful life of 

the capacitor, including instantaneous failures . 

Installation procedures
Mechanical installation

To open the capacitor bank enclosure, remove the screws holding 

the top cover . Grasp the front cover and tilt it forward and down to 

separate it from the base unit .
Inspect the internal capacitor cells to verify that no physical damage 

has occurred during shipment or handling . 
Inspect and ensure that the power conductors are secured and tight 

in their terminals by applying a gentle tug on the wires on both ends . 
Inspect the discharge resistors for any marks of damage or cracks 

and that they are seated and intact in the terminal . 
If any signs of loose or cracked discharge resistor is noticed, stop 

and do not proceed with the installation and immediately notify your 

nearest Eaton sales person for further instructions .
Mechanically secure the capacitor bank to either the wall or the floor 

using anchor fasteners . 

Electrical installation

In accordance with NEC

T

 460, conductors should be sized for at 

least 135% of the nameplate full load amps of the capacitor unit . 

NEC 460 also requires that the power factor capacitors must be 

provided with a disconnecting means and overcurrent protection .  
When connecting the capacitor bank on the load side of a motor 

starter overload relay, it is not necessary to provide additional 

disconnecting or overcurrent protection devices . 
Fuses should be rated at least 165% of rated capacitor current .  

A circuit breaker should be rated at least 135% of the rated  

capacitor current .
Eaton requires that all customer feeder supply wiring be 90 °C rated 

stranded copper wire sized and used at its 75 °C ampacity rating .
Observe all torque requirements for electrical connections . When 

making connection using crimp terminals, be sure to use the 

crimping tool recommended by the terminal manufacturer . Wire and 

cable connections having improper torque may cause loosening of 

the electrical connections resulting in localized heating or fire . The 

unit should be cleaned of any debris, metal shavings, insulation, and 

conductor strippings before being put into service .
An appropriately sized ground conductor should always be 

connected to the ground terminal . Lack of ground connection or 

improper grounding may result in electric shock or fire or inability  

of ground fault protection to operate .
Conduit entry location should be selected so as to allow the 

straightest connection to the provided mechanical lugs without 

compromising the conductors’ bending radii . Connect the capacitor 

bank by securing power conductors into the provided mechanical 

lugs and tighten to the torque provided in 

Table 3

 . Connect ground 

conductor into grounding lug and secure by tightening per torque 

requirements below .
Conduit sizes, tray sizes, and cable ampacity must be according 

to the National Electrical Code or applicable electrical codes in the 

customer’s area .
Proceed to connect the feeder cables to the disconnecting switch/ 

circuit breaker . This operation must be performed with the 

equipment completely de-energized .

Table 3.  Recommended torque

Torque based on conductor size

Torque based on bolt size

AWG

Pound-inch

Inches

Pound-inch

30–10

80

1/8

45

8

80

5/32

100

6–4

165

3/16

120

3

275

7/32

150

2

275

1/4

200

1

275

5/16

275

1/0–2/0

385

3/8

375

3/0–4/0

500

1/2

500

250–350

650

9/16

600

400

825

500

825

600–750

1000

otee:

N

Follow the lower torque value between the conductor size  

and the bolt size .

Summary of Contents for NEMA 1

Page 1: ...recautions 2 Catalog numbering systems 2 Receiving 3 Installation 3 Preparation for installation 3 Installation locations 3 Installation procedures 3 Post installation evaluation 4 Installation instructions for Unipak detuned filter 4 Electrical connections 7 Startup and commissioning 7 Alternate system voltage and frequencies 7 Operating features 8 Maintenance 8 Retorque 8 Troubleshooting 9 Gener...

Page 2: ...al energy indefinitely unless properly discharged Each capacitor is fitted with a discharge resistor designed to reduce the residual voltage in the capacitor to 50 V or less after a minute Follow all caution and warning nameplates before attempting to install operate or service the capacitor bank Before handling the capacitor disconnect all and any electrical power supply from the circuit into whi...

Page 3: ... ends Inspect the discharge resistors for any marks of damage or cracks and that they are seated and intact in the terminal If any signs of loose or cracked discharge resistor is noticed stop and do not proceed with the installation and immediately notify your nearest Eaton sales person for further instructions Mechanically secure the capacitor bank to either the wall or the floor using anchor fas...

Page 4: ...propylene with pressure interrupter Number of enclosures 2 2 a Units are designed for 60 Hz operation Consult factory for other frequencies Mechanical installation instructions for Unipak filter Reactor enclosure shall be positioned and mechanically secured next to the capacitor enclosure with a minimum 9 inch separation minimum 12 inch separation preferred between the two enclosures to allow for ...

Page 5: ... 14 2 0 2 14 30 2 14 2 14 55 2 14 2 14 32 5 14 2 0 2 14 32 5 2 14 2 14 60 2 14 2 14 35 14 2 0 2 14 35 2 14 2 14 65 14 2 0 2 14 37 5 6 250 kcmil 2 14 37 5 2 14 2 14 70 14 2 0 2 14 40 6 250 kcmil 2 14 40 2 14 2 14 75 14 2 0 2 14 42 5 6 250 kcmil 2 14 42 5 2 14 2 14 80 14 2 0 2 14 45 6 250 kcmil 2 14 45 2 14 2 14 85 14 2 0 2 14 50 6 250 kcmil 2 14 50 2 14 2 14 90 14 2 0 2 14 60 6 250 kcmil 2 14 55 14...

Page 6: ...Reactor enclosure F c F c Three phase reactor Customer interconnect terminals provided with Unipak detuned filter Ground terminal Ground terminal Bonding conductor Connection conductors and conduit provided by customer Same size as incoming conductors Customer termination terminals provided Reactor thermal switches embedded in windings normally closed Note 6 inch minimum clearance on reactor top a...

Page 7: ...ay be required to determine if the leading power factor and associated voltage rise during light load conditions are acceptable When capacitors are connected to the bus feeder motor control center or switchboard a disconnect and overcurrent protection must be provided Startup and commissioning Connect power to the capacitor bank energize through upstream switch Using an ammeter measure capacitor c...

Page 8: ...ermal overload and cleared fuse indicator lamps Maintenance The following maintenance items require the capacitor to be energized and should be performed only by trained and qualified personnel m WARNING ONLY QUALIFIED ELECTRICIANS SHOULD HANDLE THE INSTALLATION AND MAINTENANCE OF THIS CAPACITOR BANK OTHERWISE ELECTRIC SHOCK ARC FLASH OR FIRE MAY OCCUR Retorque Before handling the capacitor discon...

Page 9: ...rent in each capacitor phase and verify that it is within 10 of current rating stated on the nameplate Troubleshooting Symptom Problem Solution Cleared fuse indicator lamp lit Cleared fuse Disconnect power supply to the capacitor bank Wait at least five minutes before opening the capacitor bank cover Locate the blown fuse and its associated capacitor cell s Inspect the cells for bulging or other i...

Page 10: ... type fuses with 200 000 A interrupting capacity fuses mounted on stand off bushings solderless connectors for easy hookup of incoming line conductors Fuse indicating lights Red neon cleared fuse indicating lights are protected by transparent weatherproof guard Options Non fused units available selected sizes Heavy duty capacitor cells selected sizes Reactors Unipak detuned filter only Detuning St...

Page 11: ...1 Instruction Booklet IB157001EN Effective May 2015 Fixed capacitor banks Unipump Unipak and Unipak detuned filter low voltage 600 V and below NEMA 1 NEMA 3R outdoor enclosed versions EATON www eaton com ...

Page 12: ...ed trademark All other trademarks are property of their respective owners Fixed capacitor banks Unipump Unipak and Unipak detuned filter low voltage 600 V and below NEMA 1 NEMA 3R outdoor enclosed versions Instruction Booklet IB157001EN Effective May 2015 For technical support and application engineering assistance please contact Eaton s TRC at 1 800 809 2772 option 4 option 2 ...

Reviews: