background image

MN008006EN Manual 

Efective March 2021 

NOVA LBS Load Break Switch  

20 

www.eaton.com/cooperpowerseries 

 

 

SERVICE INFORMATION 

 

Service Requirements  

The NOVA LBS switch is designed for a minimum mechanical life of 

10,000 operations, which is class M2 according to IEC-62271-103. The 

NOVA LBS switch should be inspected every 10 years for physical 

damage and correct operation. 

Frequency of Inspection 

Because these switches are applied under widely varying operating and 

climatic conditions, service intervals are best determined by the user 

based on actual operating experience. However, solid-insulated, 

vacuum-interrupting switches should be inspected every ten years. 

Testing Operation 

This switch is used with Eaton microprocessor-based NOVA LBS control. 

Refer to the control operation manual. 

 

ADVERTISEMENT 

 

This equipment is not intended to protect human life. Follow all locally 

approved procedures and safety practices when installing or operating 

this equipment. Failure to comply can result in death, severe personal 

injury and equipment damage. 

1.

 

Check the data plate ratings

. Make sure the ratings, settings, 

and interface options on the switch data plate (Figure 6) are 

correct for the planned testing. 

2.

 

Test electrical open and close operation.

 Close and open the 

switch contacts using the microprocessor control. Confirm that 

the contacts have closed and opened by: 

A.

 

The OPEN/CLOSE contact position indicator, or 

B.

 

By a continuity check between the switch terminals. 

3.

 

Test manual open.

 

Pull the yellow manual open handle (Figure 

14) down to open the switch contacts. Confirm that the contacts 

have opened by: 

A.

 

The OPEN/CLOSE contact position indicator, or 

B.

 

By a continuity check between the switch terminals.

 

4.

 

To close the NOVA LBS contacts 

A.

 

First

 

push up the GREEN manual opening handle; 

B.

 

Close the NOVA LBS switch using the LBC control. To 

perform Manual Closing, pull down the closing lever 7 

times. 

High-Potential Withstand Testing  

The following equipment is required for this test: 

High-voltage test set

 – Must be capable of supplying suitable voltages 

for determining the dielectric withstand capability of the switch. 

Sensitive circuit breakers should be included to prevent damage in the 

event of a flashover. 

Note

: Test results for NOVA switches equipped with the internal 

voltage sensing option will be influenced by the source-to-

ground connected sensing resistor, especially if DC high-

potential testing is performed.  

 

 

ADVERTISEMENT 

 

Hazardous voltage. The switchgear (apparatus and control) and high-

voltage transformer must be in a test cage or similar protected area to 

prevent accidental contact with the high-voltage parts. 
 

 

CAUTION 

 

Radiation. At voltages up to the specified test voltages, the radiation 

emitted by the vacuum interrupter is negligible. However, above these 

voltages, radiation injurious to personnel can be emitted. See Service 

Information S280-90-1, Vacuum Interrupter Withstand Test Voltage 

Ratings Information for further information. 
 
Use the following procedures to perform high-potential withstand tests 

at 75% of the rated low-frequency withstand voltage for 60 seconds. 

Refer to Table 8 for test voltages and Figure 25 for test connection 

diagrams. 
Test results for NOVA switches equipped with the internal voltage 

sensing option will be influenced by the source-to ground connected 

sensing resistor. 

TABLE 8 – NOVA LBS withstand test voltage ratings information

 

75% of Rated Low-Frequency Withstand Voltage  

(1-minute dry) (kV rms)

 

Model 

CA 

NOVA LBS 15 

37,5 

NOVA LBS 27 

45,0 

1.

 

Approximately 0.53 mA additional leakage current per phase with internal voltage 

sensors.  

2.

 

Approximately 0.32 mA additional leakage current per phase with internal voltage 

sensors. 

 
 
 
 
 

Summary of Contents for NOVA LBS 15

Page 1: ...witch Installation and Operation Instructions Automatic Switches Manual MN008006EN COOPER POWER SERIES Efective March 2021 55 15 3481 9209 55 11 98105 1564 ApplicationCPS Eaton com Need help Contact o...

Page 2: ...edance Grounded Systems 12 Grounding on a 3 Wire Uni Grounded System 13 OPERATION 14 Electrical Operation 14 Manual Closing Loading 14 Closing 14 Opening 14 OPEN CLOSE Contact Position Indicator 14 Ho...

Page 3: ...ENT Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in mino...

Page 4: ...amage Refer to the Moving the Switch and Lifting the Switch sections If the switch is to be stored for any length of time prior to installation provide a clean dry storage area Eaton recommends transp...

Page 5: ...27 Maximum Voltage kV 15 0 27 0 Rated Basic Impulse Level kV 110 125 Power Frequency Withstand Dry one minute 60 60 Wet one minute 50 50 TABLE 2 Current Ratings Description NOVA LBS 15 NOVA LBS 27 Ra...

Page 6: ...bolt 2 0 600 MCM Cable range 630 A maximum 78 mm 3 1 in Eyebolt 4 0 1000 MCM Cable range 800 A maximum 106 mm 4 2 in Flat Pad 2 holes 630 A maximum 117 mm 4 6 in Flat Pad 4 holes 800 A maximum 121 mm...

Page 7: ...converts the control voltage from 24V DC to 12V DC to power the communication devices Figure 3 Configuration of the NOVA LBS switch with power supply through the control with input power supply from a...

Page 8: ...alled Figure 6 NOVA LBS Load Break Switch nameplate and manual opening and closing handle Opening Coil Closing spring Opening spring Lifting eyebolts Main Grounding Terminal 19 pin Receptacle Vent Val...

Page 9: ...not allow it to shift Incorrect lifting may cause damage to the equipment Moving the Switch NOVA LBS switches are transported on pallets bolted onto them When moved by forklift truck the switch must...

Page 10: ...oved prior to making or disconnecting wires to the switch terminals If the recommended torque is exceeded Refer to Figure 10 for terminal identification of the NOVA LBS Terminal connection to copper c...

Page 11: ...sult in personal injury Before disconnecting the control cable open the NOVA LBS switch contacts and open the disconnect switches CAUTION Disconnect the battery and external power sources from the con...

Page 12: ...lightning arresters Grounding of the switch head and tank Grounding of the transformer tank Grounding of the control cabinet Grounding of the SCADA equipment Figure 11 Recommended grounding method for...

Page 13: ...emote devices can produce exported potential causing equipment damage or personal injury CAUTION Hazardous Voltage Do not use a shared low voltage network to power the switch control unless the networ...

Page 14: ...nd to the NOVA LBS Load Break Switch through the LBC control the opening solenoid activates the opening spring and the mechanism is engaged instantly The NOVA LBS Load Break Switch uses a hydraulic da...

Page 15: ...oltage sensing option connections when installing the control as indicated in these Service Information manuals Verify correct grounding of the NOVA switch and control prior to making any high voltage...

Page 16: ...tacle connections are made Improper cable connections can result in damage to the switch and or control Complete the control programming before making the high voltage line connections Refer to the Op...

Page 17: ...4 The eyebolt flat pad and stud terminals are made of copper alloys Eaton recommends terminal connection to copper wires to optimize the electrical connection Aluminum cables may produce aluminum oxi...

Page 18: ...ting Hanger A pole mounting hanger Figure 18 which bolts directly to the switch frame is available for pole mounting installation Note All dimensions are mm inches Dimensions shown are approximate Fig...

Page 19: ...ccessory Figure 23 can be bolted to the switch frame and pole mounting hanger for the addition of inboard and outboard arresters The arresters are not included with the brackets Note All dimensions ar...

Page 20: ...A First push up the GREEN manual opening handle B Close the NOVA LBS switch using the LBC control To perform Manual Closing pull down the closing lever 7 times High Potential Withstand Testing The fol...

Page 21: ...e Test results for NOVA LBS equipped with the internal voltage sensing option will be influenced by the source to ground connected sensing capacitor especially if DC high potential testing is performe...

Page 22: ...er check switch control battery level Check the fuses on the DC DC converter board in the control cabinet Check that the closing spring is fully charged Check that the motor is charging the spring Uni...

Page 23: ...do recept culo na Chave NOVA LBS PIN COLLO SIGNAL A ORANGE BLACK OPENING B BLUE BLACK CLOSING C BLACK WHITE Vcc D RED WHITE Ia E GREEN WHITE Ib F BLUE WHITE Ic G BLACK RED NEUTRAL CURRENT H ORANGE J K...

Page 24: ...VS LOAD SIDE C IVS LOAD SIDE B IVS LOAD SIDE A IVS SOURCE SIDE B IVS SOURCE SIDE A MANUAL SIGNAL BLOCK CLOSE OPEN DESCRIPTION RECEPTACLE 19 PINS CONTROL CABLE AUXILIARY SWITCH MICROSWITCH OPEN LEVER C...

Page 25: ...Publication No MN008006EN 15 Eaton Cooper Power and NOVA LBS are valuable trademarks of Eaton in the U S and other countries Youare not permitted to use these trademarks without the prior written con...

Reviews: