TROUBLESHOOTING
If the NOVA LBS does not perform as described in the OPERATION
section of this manual, the following information may assist in
troubleshooting:
Unit Will Not Close
•
Make sure the GREEN manual opening handle is completely up.
•
Check all cables for proper connection.
•
Verify that the control has power.
•
Upon loss of ac power, check switch control battery level.
•
Check the fuses on the DC/DC converter board in the control
cabinet.
•
Check that the closing spring is fully charged.
•
Check that the motor is charging the spring.
Unit Will Not Open Electrically
•
Check all cables for proper connection.
•
Verify that the control has power.
•
Check the fuses on the DC/DC converter board in the control
cabinet.
•
Check that the opening spring is fully charged.
Undesired Closing
•
Check that the closing coil is powered.
•
Check that Sync Check / LS adjustments in the LBC control.
Undesired Opening
•
Check that the closing coil is powered.
•
Check that adjustments in the LBC control.